IGS-NT Installation Guide
68
A
U
T
C
O
M
A
O
U
T
+
N
OTE
:
Jumper settings for Analog Inputs and Outputs is the same for all the controllers. Not all
analog inputs and outputs are available in all hardware modifications.
AOUT COM is internally connected to controller 0 VDC power supply.
7.10.2.
Speed Governor Output
SG COM
SG OUT
PWM
SG COM
SG OUT
VoutR
SG COM
SG OUT
Vout
Pulse Width Modulation 500÷3000 Hz / 5V /
10mA max (default frequency 1200 Hz, may be
changed by setpoint
Sync/Load ctrl:SpdGovPWM rate
)
V-
outR range: ± 10 VDC via 10 kΩ
V-out range: ± 10 VDC
H
INT
SG COM is internally connected to controller 0VDC power supply. IS-NT-BB and IS-NTC-BB
have the same jumper position.