IGS-NT Installation Guide
117
AVRi outputs can be connected as symmetric: OUT1-OUT2 or asymmetric OUT1-OCOM or
OUT2-OCOM.
•
Potentiometer on the AVRi defines maximum OUT1, OUT2 voltage range.
•
Use symmetric (OUT1,OUT2) AVRi output to connect the AVRi to AVR auxiliary
voltage input.
•
Use asymmetric output if an external AVR potentiometer has to be replaced with
AVRi.
•
AVRi output voltage should change generator voltage typically in range
10 % of
Nominal voltage.
•
For more details please refer to Installation guide
– chapter AVR interface examples.
100.0 %
10 V
0 V
AVR DCout bias
0 %
AVRi p
ot set to
minimu
m
2 V
AV
Ri
po
t se
t to
ma
xim
um
OUT1
– OCOM [V]
100.0 %
10 V
0 V
AVR DCout bias
0 %
AVRi pot set
to minimum
2 V
AVR
i po
t se
t to
max
imu
m
OUT2
– OCOM [V]
AVRi Out1 or Out 2 to GND output voltage depends on AVRi trim setting
[V]
100.0 %
AV
R
i p
ot
=
m
ax
im
um
AVR DCout bias
10 V
Out1 to Out2
0 V
0 %
-10 V
AVR
i po
t =
min
imu
m
50 %
AVRi output voltage
Out1 -
OCOM
Out2 -
OCOM
Out1
–
Out2
Bias \
Pot
Min
Max
Min
Max
Min Max
0 %
0
0
2
10
- 2 V -10
V
50 %
1
5
1
5
0 V
0 V
100 %
2
10
0
0
+ 2
V
10 V
AVRi Out1 to Out 2 output voltage
17.2.2.
Voltage control adjustment
1) Set
Voltage gain
,
Voltage int
to zero and
AVR DCout bias
to 50%.
2) Start always with AVRi pot min adjustment (fully counterclockwise).
3) Start the gen-set in MAN Mode to nominal speed, without load.
4) Adjust generator voltage to nominal value by the potentiometer present on the AVR. If
there is no potentiometer on the AVR, use setpoint
AVR DCout bias
to adjust the
nominal voltage
.
5) Change
AVR DCout bias
to 0% and 100% to check generator voltage control range
(typically
10 % of nominal voltage). Adjust voltage control range by AVRi trim.
6) Set
AVR DCout bias
to be Nominal voltage on generator (50%).
Summary of Contents for IG-NT
Page 24: ...IGS NT Installation Guide 24 5 2 3 InteliVision 5 5 2 4 InteliVision 8...
Page 75: ...IGS NT Installation Guide 75 9 Recommended Wiring 9 1 SPtM application...
Page 76: ...IGS NT Installation Guide 76 9 2 SPI application...
Page 77: ...IGS NT Installation Guide 77 9 3 MINT application...