IGS-NT Installation Guide
148
20.17.5. RS232 interface
Maximal distance
0m
Speed
p to 19.2kbps (depends on ECU type
connected)
20.18. I-LB
Voltage supply
-36V DC
Consumption
,1A depend on supply voltage
Operating temperature
-30..+70
o
C
Mechanical dimensions:
5 x 96 x 43 mm , DIN rail (35 mm)
mounted
Interface to modem or PC
S232, RS422, RS485, (USB
– I-LB+
version)
Interface to controller
AN
20.19. IG-IB
Voltage supply
-36V DC
Consumption
,1A depend on supply voltage
Mechanical dimensions:
5 x 96 x 43 mm , DIN rail (35 mm)
mounted
Interface to controller
S232 or CAN
Interface to modem
S232
Interface to Ethernet
J45 (10baseT)
Operating temperature
-30..+70
o
C
Storage temperature
-30..+70
o
C
20.20. I-RBxx
Number of relays:
6 or 8 in sockets
Nominal voltage:
4 VDC
Voltage range:
6,8
– 36 VDC
Relay opens at:
0% of nominal voltage
Electric / mechanic cycles:
00 000 / 10 000 000
Operating temperature range:
40°C to 70°C
Maximal load:
6 A resistive load at 24VDC
4 A inductive load at 24 VDC
(I-RBxx-231)
2 A at 231VAC
Contacts protection:
aristor 14DK390
20.21. IG-MTU
Primary voltage Ph-Ph
x400 VAC / 50Hz (3x480 VAC / 60 Hz)
Secondary voltage Ph-N
x 230 V AC ( 3x277 VAC / 60 Hz) , 5 VA
Mechanical dimensions:
5 x 95 x 60 mm , DIN rail (35 mm)
mounted