Digital fire detection control panel
LYON REMOTE PLUS
37
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
1.5.5.- Repeaters
1.5.5.1.- Installation
The repeater must be fixed on a vertical wall face. The side slots must be left free for heat to escape. The
dimensions and the pre-drilled holes for cable entry are shown in the following diagram.
Figure 15
. Repeater box
The LYON control panel allows up to 15 repeaters to be connected to it. For this, a 4-wire connection of
1.5 mm
2
wires (two for power supply and two for communication, for the RS485 line) must be used.
The two wires for the RS485 line are to be connected from the control panel’s back panel to the terminals
of each control panel labeled as “REPETITOR” in the front label.
The two power supply wires are to be connected from the 30V output of the control panel’s power supply
to the terminal labeled as 30 V of the corresponding repeaters. The repeaters must be connected as shown
in figure 16.
Up to 3 repeaters can be connected to the Lyon control panel’s power supply 30V output. From 4 to
15 repeaters must be fed from the 30V output of an auxiliary power supply (FAE).
For connecting the repeaters, both the communication and 30V power supply cables must be
2 x 1.5 mm
HALOGEN-FREE SCREENED BRAIDED CABLE, up to a maximum cable length of 1200 metres.
On completing the installation, a 120 Ohm resistor must be connected between the terminals A and B in the
“REPETITOR” connector of the last repeater connected.
DISCONNECT the 110~230V MAINS voltage and the BATTERIES
before handling the inside of the control panel or the repeaters.