Digital fire detection control panel
LYON REMOTE PLUS
48
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
2.2.3.- Power supply auxiliary outputs and charging of power source batteries.
-Battery charger and auxiliary power supply outputs
Power supply board:
30v DC output
supply for battery
charger control
CPU and sirens
Power supply
Supply fuse
8 A
Battery fuse
5 A
Bat. charger fuse
1 A
30V fuse
2 A
S1 Siren fuse
2 A
S3 Fault fuse
1 A
C
O
M
M
O
N
+24V
C
O
M
M
O
N
NC
NA
C
O
M
M
O
N
+24V
GND
GND
+30V
+30V
GND
+24v
M
ONIT
ORE
D
S
IRE
N
AL
AR
M
OUT
P
UT
F
AU
L
T
OUT
P
UT
AU
X
IL
IARY
3
0
V
O
UT
P
UT
24V
BA
T
T
E
RIE
S
Figure 22.
Power supply auxiliary outputs
S1 Sirena Sounder
This output of the siren is monitored and protected by means of a fuse. If a delay is required this can be
done as seen in chapter “3.Configuration.”
The installation of sirens will be performed according to the schematic of
Figure 24
. This output is
activated whenever an alarm occurs in the system and if a delay is programmed waits until the timer
expires, and then it will activate .
It is only deactivated when there is no alarm in the system.
S2 Alarm
Voltage-free output exit. It is activated whenever an alarm occurs in the system. It is only deactivated
when there is no alarm in the system.
S3 Fault
Monitored fault output and protected by means of fuse, to which a delay can be applied by means of
the configuration menu, see 3 chapter configuration. It will be activated whenever there is a fault in the
system and the programmed delay has passed. It is only deactivated when there is no fault in the
system.
Auxiliary 30V output
The 30V output is used to provide power to addressable modules or relays or other external devices.
This output is monitored and protected by means of a fuse.