Digital fire detection control panel
LYON REMOTE PLUS
52
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
Auxiliary 30V supply is required for the MYOA/F, MDA1Y and MDA2Y modules
2.3.3.3.- Connection of the flashing internal 24V Sounder (SIR24F)
Elements needed for its correct installation:
1 Resistance of 33 KΩ; in the event of the sounder being connected to the general sounder, the
resistance should be 4K7, which is included in the control panel and/or the modules.
1 BY252 Diode; two diodes are included with each Lyon control panel.
Figure 27
. SIR24F Connection schematic
2.3.3.4.- External Siren 24V alarm box (CAEC)
• Red outdoor siren made of ABS plastic.
• Built-in back cover to protect all internal circuitry.
• They work as 24V power sirens.
• Piezoelectric speaker.
• Certified EN54-3 type B.
NOTE:
EOL: 33KΩ when connected to module
EOL: 4K7 when connected to the control panel
Figure 28
. CAEC Connection schematic