Digital fire detection control panel
LYON REMOTE PLUS
46
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
2.2.- Wiring Lyon addressable system
Connection of the
Lyon addressable system
will be carried out with
2 x 0.7 mm up to 2 x 2.5 mm
BRAIDED CABLE SCREENED HALOGEN FREE,
both the loops as well as the sounders, KMAY
connected elements, fault outputs and 30 volt auxiliary supplies.
The connection of the loop allows elements installed in the loop or in branches with wiring distances
between the elements and the control panel of lengths of up to 1500 meters.
Connection of the loop elements will be carried out in accordance with the schematics indicated in figures
2, 3, 4, 5, 6, 7, 8, 9,10,11,12,13.
To avoid the dust entering in the sensors , wich may cause a performance degradation (A30XTA,
A30XHA or A30XHTCO), the red cover protector should be put on sensors while there is work on
progress in that building.
Once everithing is operational, all covers from all sensors
SHOULD BE REMOVED
, otherwise they will
not work properly or not work at all.
A list must be made for each loop with the location, type and programming number of each element, this
programming number goes from 1 to the 65533, see the example in the following table:
Loop: 01
POINT
Programming no.
Label
Type
Notes
1
12757
ROOM 101
A30XHA
2
12432
ROOM 102
A30XHA
3
4767
BUTTON P1
PUCAY
4
6982
CORRIDOR P1
MDA1Y
DISCONNECT the 110~230V Voltage circuit and BATTERIES
before accessing the interior of the control panel.
2.2.1.- Electrical supply network.
Power supply is 110~230V ±10% 50 - 60 Hertz. Connection will be made by means of 3 strands with a
minimum section of 1.5mm the connection of the earth cable to the terminal of the switched supply being
obligatory. The maximum consumption for a control panel of up to 8 loops is 150 W and for control panel
of 9 to 20 loops is 300W.
DISCONNECT the 110~230V Voltage circuit and BATTERIES
before accessing the interior of the control panel.
Do not cut power to the control panel during the boot process.
Such action may cause malfunction of the unit.
Switched Source
Figure 20.
Switched Mode Power Supply (SMPS)