1.5.4. - Modules
1.5.4.1- Master detection module (KMAY)
Microprocessed addressable device (with short-circuit isolator) installed as one
more element in the loop.
This is a device that allows connecting conventional detectors and/or manual call
point inside an addressable fire detection system acting as a bridge between the
addressable detection system and the conventional one.
In the “Zone C” terminal, a maximum of 10 conventional call points can be
installed. In the “Zone D” terminal allows up to 20 temperature detectors
(A30XT, A30XV) or 15 elements between conventional smoke detectors
(A30XH, A30XHS) and manual call points. Both terminals are monitored by an
end of line capacitor, 10 µF/63V. In this way the status of the line can be known if
it is open, shorted to ground or a device entered in alarm state.
The flashing of the transparent red LED indicates communication with the control
panel, and if it remains on it indicates the alarm status of a detector or manual call
point connected to this module.
This module has an output for activation of a remote indicator which will be activated when alarm status is
reached. The Master Detection Module takes the power supply from the loop.
The Master Detection Modules is placed in a rectangular, heat-resistant ABS box.
The
KMAY
device complies with EN 54-18 with the conformity mark awarded by AENOR.
Note: To determine the number of KMAY it can be installed, consult the devices limit per control
panel table (Chapter 1.5)
Figure 3
. Wiring diagram KMAY