background image

 

1. OPERATION.

Is a compact automatic control  device  designed for the single-phase or three-phase pump´s (depending on model) automation, 
with an electronic system managed by a software  responding to the rigorous requirements of efficiency and safety of the most 
important builders of pumps. It includes a frequency inverter that regulates the speed of the pump  in order to keep constant the 
pressure independently of the flow given.
The system incorporates a LCD screen where the parameters configuration is very easy and intuitive. Once the configuration 
parameters are introduced, the device manages the start-up of the pump and the frequency inverter. It  assures a constant 
pressure and an important costs reduction because at any time the control will feed the system with the right and necessary output, 
obtaining a maximum energetic efficiency. In order to establish the ideal pressure in the installation is suitable to consider  following 
criteria:

Hm

:     Max. water column height in m. It depends on the number of floors and it corresponds  to the height from the pump to the 

last floor. Every 10 m of height corresponds approximately to 1 bar (0.98) bar.

Pw

:      Available minimum pressure in last floor (usually 1.5 bar).

Pc

:       Pressure drop. It can be considered with a simplified criteria as 0.033 bar/m.

Prmin

: Minimum resultant pressure. It is the sum of the previous pressures and it will be the operating pressure of the pump.

Example for a 5 floors building (15 m) with pump placed at level 0:

Hm

 =15 m 

@

 1.5 bar 

Pw

 = 1,5 bar      

Pc

=15 x 0,033 bar 

@

 0,5 bar     

Prmin

 = 1,5  + 1,5  + 0,5  = 3,5 bar

              MASTER AND SLAVE OPERATION

The group MASTER-SLAVE is constituted by a device configured as SPEEDMATIC  MASTER - responsible of the group´s control - 
and a SPEEDMATIC  configured as SLAVE controlled by the master device. 
Due to the alternating sequence of operation, the SPEEDMATIC configured as MASTER began the first cycle as MAIN device - its 
pump is the first to start - but in the next cycle it becomes SECONDARY - its pump is the  second to start - and so on. Therefore, 
the fact that a device is configured as MASTER involves control of the group but this fact does not avoid its work alternately as 
SECONDARY device.

2. CLASSIFICATION AND TYPE.

According to EN-60730-1 this product  is a device of independent assembly, type 1B with software of class A. Control circuit for 
alternating current motor with power factor cosφ 

≥ 

0,6. Pollution Degree 2. Rated impulse voltage: 2500V/CATII.  Class of 

disconnection 1Y (electronic disconnection).

3. MAIN CHARACTERISTICS.

n

DN inlet port G1 1/4 ” male ISO 228.

n

DN outlet port G1 1/4 ” male ISO 228.

n

Frequency inverter for the pump control.

n

Control and safety system against over-intensities.

n

Control and safety system against dry operation.

n

ART 

function (Automatic Reset Test). If the device has been stopped due to the action of the safety system against over-

intensities, the 

ART

 tries to connect the pump, with a programmed periodicity because the water supply could have been 

restored

n

Automatic restore system after an interruption of power supply. System is activated in AUTOMATIC mode keeping the 

configurationparameters (see “CONFIGURATION” chapter).

n

Inside pressure transducer.

n

Control panel (see chapter 7): 2 digits display, pushbuttons, led lights and digital gauge providing  instantaneous lecture of 

pressure.

n

Register of operational controls: infomation about operating hours, counter of starts, counter of connections to the power supply.

n

Connections for detection of minimum water level in aspiration tank. This system is independent of the safety against dry 

operation. Is optional.

n

Register of alarms: information about type and number of alarms since the starting up of the device.

n

  Mode MASTER & SLAVE. Communication with another device SPEEDMATIC to work in group. Optional.

       

4. TECHNICAL CHARACTERISTICS.

n

Type  

 

        EASY 09MM 

EASY 12MM  

EASY 06MT  

Easy 10 MT 

n

Power supply voltage 

        ~1x230 ± 20% V  ~1x230 ± 20% V 

~1x230 ± 20% V  

~1x230 ± 20% V  

n

Frequency 

 

        50/60 Hz 

50/60 Hz 

 

50/60 Hz 

 

50/60 Hz

n

Max. current each phase 

        9A  (~1  230 V) 

12A  (~1  230 V) 

6A  (~3  230 V) 

10A  (~3  230 V)

n

Max. peak of current        

        20% during 10" 

20% during 10" 

20% during 10" 

20% during 10"

n

Max. operating pressure  

        15 bar  

15 bar 

 

15 bar 

 

15 bar

n

Max. set pressure 

        0.5

÷

8 bar  

0.5

÷

8 bar   

0.5

÷

8 bar    

0.5

÷

8 bar 

n

Protection index   

        IP55   

IP55 

 

IP55 

 

Ip55

n

Max. water temperature 

        40ºC   

40ºC 

 

40ºC 

 

40ºC

n

Max. environment temperature       0-50ºC 

0-50ºC 

 

0-50ºC 

 

0-50ºC

n

Max. flow 

 

        10.000 l/h 

10.000 l/h   

10.000 l/h   

10.000 l/h

n

 General protection fuse 

        10A   

16A 

 

16A 

 

20A

BEFORE INSTALLATION AND USE READ THE FOLLOWING INSTRUCTIONS CAREFULLY. THE MANUFACTURER DECLINES ALL RESPONSABILITY IN 
THE EVENT OF ACCIDENT OR DAMAGE DUE TO NEGLIGENCE OR FAILURE TO OBSERVE THE INSTRUCTIONS DESCRIBED IN THIS MANUAL OR IN 
CONDITIONS THAT DIFFER FROM  THOSE INDICATED ON THE DEVICE. TECHNICAL MODIFICATIONS RESERVED

english

-8-

M

M

Summary of Contents for Speedmatic Easy 06MT

Page 1: ...TION AND OPERATING INSTRUCTIONS ISTRUZIONI D INSTALLAZIONE E USO INSTRUCTIONS POUR L INSTALLATION ET L EMPLOI INSTRUCCIONES PARA LA INSTALACI N Y UTILIZACI N MONTAGE UND GEBRAUCHSANLEITUNGEN EN IT FR...

Page 2: ...es consequence des gouttements par d t riorations in vitables de robinets valves etc ainsi que poyr viter le marteau de l eau produits mormalment par electrovalves ou valves avec un pas de d bit consi...

Page 3: ...RATION CE DE CONFORMIT 12 ALARMES INSTRUCCIONES PARA LA INSTALACI N Y UTILIZACI N 20 23 1 FUNCIONAMIENTO 2 CLASIFICACI N Y TIPO 3 CARACTERISTICAS GENERALES 4 CARACTER STICAST CNICAS 5 INSTALACI N HIDR...

Page 4: ...TO CORPO Easy CONNEXIONS DU CORPS Easy CONEXIONES CUERPO Easy ELEKTRISCHE ANSCHL SSE u w v L m 5 25 1 5 25 50 u Class C2 4 MAX MIN LEVEL CONNECTION COLLEGAMENTO LIVELLO CONNEXION NIVEAU CONEXION NIVEL...

Page 5: ...on generale Alimentazione elettrica v 2 S mm 2 5 1 4 L m 5 25 1 5 25 50 u u v Three phase motor connection Collegamento motor tre fasi Connexion motor triphas e Conexi n motor trif sico Dreiphasen Mot...

Page 6: ...A Los accesorios w x yy son recomendables pero no imprescindibles B En el caso del tanque hidroneum tico se recomienda su utilizaci n en instalaciones donde se pretenda evitar el golpe de ariete HINWE...

Page 7: ...to Avviti la copertura e la PG ES 1 Desatornillar la tapa y aflojar el PG pasacables situado en su base 2 Introducir el cable de comunicaciones a trav s del PG 3 Sacar la regleta de conexiones de su a...

Page 8: ...Control circuit for alternating current motor with power factor cos 0 6 Pollution Degree 2 Rated impulse voltage 2500V CATII Class of disconnection 1Y electronic disconnection 3 MAIN CHARACTERISTICS n...

Page 9: ...throw the PG cable gland located in the bottom lateral of the device See Fig 9 WARNING Wrong connections could spoil the electronic circuit The manufacturer declines all responsability in damages caus...

Page 10: ...as 2 SLAVE ENTER to validate 7 In case 1 MASTER is selected it can be ajusted a maximum time of continued functioning After the configurated time t A of a continued functioning an alternance will be f...

Page 11: ...r could be blocked Verify intensity values introduced in the configuration menu Once the problem have been solved the operation will be restored going to the SET UP menu see the chapter configuration...

Page 12: ...in ausiliare la sua pompa la seconda in avviarsi e cos successivamente Cio il fatto che un dispositivo stia configurato come MASTER implica il controllo del gruppo per questo non impedisce che funzio...

Page 13: ...struzioni fig 9 ATTENZIONE I collegamenti erronei possono danneggiare irrimediabilmente il circuito elettronico 7 PANNELLO DI COMANDI 1 Schermo 2 digiti Nella situazione di lavoro pu indicare la press...

Page 14: ...e lo Slave come 2 SLAVE ENTER per convalidare 7 Nel caso che sia selezionato 1 MASTER si pu regolare un tempo massimo di funzionamento continuo Dopo il tempo configurato t ALT di funzionamento continu...

Page 15: ...adeguato Una volta risolto il problema di detta pompa per restabilire il suo funzionamento si andr sul menu INSTALLAZIONE vedere confugurazione e introdurre i valori di intensit adeguati A3 POMPA CAN...

Page 16: ...nt comme dispositif auxiliaire 2 CLASSIFICATION ET TYPE Selon EN 60730 1 l quipe est un dispositif d assemblage ind pendant du type 1B avec software de classe A Circuit de commande moteur pour courant...

Page 17: ...lisera un c ble du type 4x0 25 mm qui sera introduit par le PG des c bles situ dans la partie inf rieure de la couverture du dispositif Voir fig 9 ATTENTION Le fabricant d cline toute responsabilit ca...

Page 18: ...lage de groupe M S l appareil ma tre doit tre configur comme 1 MASTER et l esclave comme 2 SLAVE ENTER pour valider 7 Dans le cas o 1 MASTER est s lectionn c est possible de r gler un temps maximum de...

Page 19: ...me pour r tablir son fonctionnement il faudra aller au menu INSTALLATION voir configuration et introduire les valeures d intensit correctes A3 POMPE DEBRANCHEE Alarme d finitive DESCRIPTION le Speedma...

Page 20: ...l ciclo siguiente se convierte en auxiliar su bomba es la segunda en ponerse en marcha y as sucesivamente Por lo tanto el hecho que un dispositivo est configurado como MASTER implica el control del gr...

Page 21: ...ables situado en la parte inferior de la tapa del dispositivo Ver fig 9 ATENCION Las conexiones err neas pueden da ar irremediablemente el circuito electr nico El fabricante no se responsabilizar de l...

Page 22: ...s para el dispositivo que pretendamos configurar como 2 SLAVE Al pulsar ENTER validamos y salimos del men de configuraci n 7 En modo 1 MASTER En caso de no finalizar un ciclo por consumos continuados...

Page 23: ...Verificar que los datos introducidos en el menu de configuraci n respecto el consumo de la bomba sea el adecuado Una vez solucionado el problema para restablecer el funcionamiento de la bomba se deber...

Page 24: ...KLASSIFIKATION UND TYP Gem EN 60730 1 ist das Ger t eine Vorrichtung f r die selbst ndige Montage vom Typ 1B und ist mit Software der Klasse A ausgestattet berwachungsstromkreis f r den Wechselstromm...

Page 25: ...rnimmt keine Haftung f r Sch den am Ger t die auf einen fehlerhaften Anschluss zur ckzuf hren sind 7 STEUERTAFEL 1 Display mit 2 Ziffern W hrend des Betriebs k nnen der aktuelle Druck bar die aktuell...

Page 26: ...e ber die Pfeiltasten den gew nschten Nennwert der Stromst rke f r die Pumpe ein um den thermischen Schutz zu aktivieren F r das Ger t Easy09 MM ist ein Wert zwischen 0 und 9 A einzugeben Der standard...

Page 27: ...ebung der St rungsursache muss f r die neuerliche Inbetriebnahme der Pumpe ber das entsprechende Men feld Zugriff auf die EINSTELLUNG ausge btunddieerforderlichenStromst rkewerteeingegebenwerden A3AUS...

Page 28: ...e europee armonizzate UNE EN 60730 1 1998 A11 1998 A2 1998 A14 1998 A15 1998 A20 1998 A17 2001 ERRATUM A1 2001 A18 2003 UNE EN 60730 2 6 1997 A1 1998 A2 1999 CORR A1 2001 CORR A2 01 UNE EN 61800 3 Cla...

Reviews: