REGISTER OF OPERATION DATA AND ALARMS.
By using simultaneously
MENU
+
p
during 3” is acceded to
REGISTER OF OPERATION DATA AND ALARMS
, by mean of
ENTER
we can
advance through the sequence, once finished the sequence it returns to the main display. This is all the sequence:
n
DRY RUN. Number of dry-running alarms.
n
OVERLOAD P1. Number of overload alarms in pump 1.
n
OVERLOAD P2. Number of overload alarms in pump 2.
n
LEVEL. Number of level alarms.
n
PRESSURE SENSOR. Number of damaged pressure sensor alarms.
n
OVERTEMP P1. Number of alarms by excessive temperature in pump 1.
n
OVERTEMP P2. Number of alarms by excessive temperature in pump 2.
n
HIGH VOLTAGE. Number of alarms by excessive temperature.
n
LOW VOLTAGE. Number of alarms by excessive temperature.
A L A R M
R E G I
S
T
E
R
A 1
D R Y
R U N
0
A 2
O V E R L O A
D
P
1
0
A 3
O V E R L O A
D
P
2
0
A 4
L E V E L
0
A 5
P R E S S U R
E
S
E
N
S
0
A 6
O V E R T E M P
P
1
0
A 8
H I
G H
V O
L
T
A
G
E
0
A 1 4
S H O R T C
I
R
C
P
1
0
A 7
O V E R T E M P
P
2
0
A 9
L O W
V O L
T
A
G
E
0
A 1 5
S H O R T C
I
R
C
P
2
0
F U N C T
I O N
R
E
G
0
S T A R T S
C O U N
T
P
1
0
S T A R T S
C O U N
T
P
2
0
O N
T I M E
P 1
0
O N
T I M E
P 2
0
T I M E
I N V E R
T
E
R
0
M A I N S
C O U N
T
E
R
1
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
MENU+
p
ENTER
A 1 3
M I N . P R
E
S
S
0
n
MIN PRESS. Number of minimum pressure alarm.
n
SHORTCIRC P1. Number of short circuit alarms in pump 1.
n
SHORTCIRC P2. Number of short circuit alarms in pump 2.
n
STARTS COUNT P1. Sows the number of starts of pump 1.
n
STARTS COUNT P2. Shows the number of starts of pump 2.
n
ON TIME P1. Shows the operating time of the pump 1 in hours.
n
ON TIME P2. Shows the operating time of the pump 2 in hours.
n
TIME INVERTER. Shows the operating time of the inverter in hours.
n
MAINS COUNTER.Shows the number of connections to the electric supply.
M E N U
E X P E R T
M A X .
F R E Q U E N C Y
5 0 . 0
H z
P R O P O R T I O N
A
L
9 2
I
N T E G R A L
1 0 0
A C C E L E R A T I
O N
4 0
D E C E L E R A T I
O N
5 0
M O T O R
T Y P E
T H R E E P H A S E
U
V
W
S W I T C H I N G
F
R E Q .
8
K H z
Using
pq
it can be adjusted the desaceleration. Rank 5-20 (Hz/s). Press
ENTER
to
confirm.
Using
pq
it can be adjusted the desaceleration. Rank 5-20 (Hz/s). Press
ENTER
to
confirm.
Using
pq
it can be adjusted the commutation frequency 8KHz o 4KHz. Press
ENTER
to
confirm. For installations with submersible pumps or where the cable of the device to the
pump exceeds 20m, it is advisable to work in a commutation frequency of 4Khz.
PI parameter, factory set. For any doubt contact with the manufacturer.
To start the configuration secuence press
MENU + ENTER
during 3"
By mean of keys
pq
it can be adjusted the maximum working frequency.
By mean of keys
pq
it can be adjusted the motor type: Single phase/Three phase.
In case of single phase disconnect black cable. (fig.4)
EXPERT MENU.
Special configuration, there is no need to adjust these values, they are factory set.
Using
pq
we can change the values and press
ENTER
for validation. Whenever we want to quit the configuration sequence press
MENU
. After every
ENTER
it will appears automatically the different screens that constitute the configuration sequence.
-11-