 ALARMS FOR SINGLE ASSEMBLY.

In case of simultaneous alarms, quit the automatic mode and go to manual mode, pressing  the pushbutton 

AUTOMATIC ON/OFF

 (led light 

PUMP will turn off). Using key

 

pq

will be displayed the succesive alarms. Once visualized, for leaving the menu,  press 

ENTER

 returning to 

MANUAL

 mode. 

A1 DRY RUNNING (  Failure verification   Final failure)

 

 

DESCRIPTION: i

f the system detects dry running during more than 10 seconds, it will stop the pump and the ART (Automatic ResetTest) will 

be activated. 
SYSTEM REACTION: after 5 minutes ART system will start again the pump during 30 seconds, trying to restore the system. In case of 
persistent lack of water, it will try it again every 30 minutes for 24 hours. If after all these cycles , the system still detects lack of water, pump 
will remain permanently out of order until the damage will be repaired.

SOLUTION: d

ry running,  it has been activated the safety system: you should verify the feeding of the hydraulic network. The pumps can be 

primed using the push-button START/STOP ( the led light AUTOMATIC should be off, if it is not, press the push-button to disable it).

Special case:

 if the pump cannot provide the programmed pressure (configuration mistake) the unit reacts as it was dry-running.

Special Case 2: 

this device manages the dry running control through the nominal current consumption of the pump. It must be 

verified  the introduced current consumption in the setup menu.

A2 OVER-LOAD PUMP 1 - A3 OVER-LOAD PUMP 2 (   Failure verification   Final failure)

 

 

DESCRIPTION: t

he  pump is protected against over currents by mean of the intensity values established in the installation menu. These over 

currents are produced generally by dysfunctions in the pump or in the electric supply.
SYSTEM REACTION: when detecting the thermal failure, the pump will be automatically stopped. The   system will try again to restart the  
pump when the demand of consumption require it. The control system will carry out 4 attempts in this circumstances. If the system remain 
locked after the 4th attempt, the  pump will remain definitively out of order.

SOLUTION: v

erify the state of the pump, for example the impeller could be blocked. Verify intensity values introduced in the configuration 

menu. Once the problem have been solved the operation will be restored  going to the “SET UP” menu ( see the chapter configuration) and 
configuring the adequated intensity values.

A4 LEVEL(  Verification failure)

 

DESCRIPTION: the device has a extern exit that if it si configurated as “LEVEL”, will activate this alarm.
SYSTEM RESPONSE: The functioning of the system is interrupted until the state of the level.
SOLUTION: Check conections and/or configuration of the extern exit as function “LEVEL”.

A5 TRANSDUCER (  Final failure)

 

DESCRIPTION: t

he transducer damages are showed in the LCD screen.

SYSTEM REACTION: the device operation is interrupted.

SOLUTION: 

 

check the external pressure transmitter.

A6 EXCESSIVE TEMP. PUMP 1 - A7 EXCESSIVE TEMP. PUMP 2   Final failure

 

DESCRIPTION: t

he system has a cooling device to keep the INVERTER  in optimum working conditions.  

SYSTEM REACTION: if an excessive temperature is reached the own system leaves the inverter out of service and as consequence the pump 
too.

SOLUTION: v

erify the temperature environment should be under 50 ºC.  Contact with technical service.

A8 OVERVOLTAGE -  A9 UNDERVOLTAGE (  Failure verification)

 

DESCRIPTION: the device has an electronic safety system against overvoltages and too low supply voltages.
SYSTEM REACTION: in case of overvoltage or undervoltage the system remains stopped until an adequate value of voltage is reached. In this 
case,  the system is automatically restored.
SOLUTION: check the electric supply.

12 MAX PRES ( )  Final failure

 

DESCRIPCIÓN: the device has an electronic system to protect maximum pressures.
RESPONSE OF THE SYSTEM:   If the device detects a higher pressure than the configurated as “P.MAX” during a longer time than the 
configurated as “t P.MAX” it will happen a final failure stopping the system.
SOLUTION: Check consign pressure and maximum pressure. 

A13 P. MIN ( ) Final failure

 

DESCRIPTION: the device has a protection system for low pressures.
SYSTEM RESPONSE: If the device detects a pressure lower than the configurated as “P.MIN” during a longer time thas the configurated as “t 
P.Min” it will appear a final failure stopping the system.
SOLUTION: Check for leakages on the instalation and the value of the minimum pressure configurated.

A14 SHORTCIRCUIT PUMP 1 - A15 SHORTCIRCUIT PUMP 2(  Final failure)

 

DESCRIP

TION: the device has an electronic system for protection against short circuits as well as peaks of current.

SYSTEM REACTION: the pump stops and then it starts again -performing  4 successive attempts. If the problem is not solved, the  pump will 
remain definitively out of order. 
SOLUTION: check the pump, if the problem persists, contact the technical service.

A16 PUMP 1 OFF - A17 PUMP 2 OFF 

inal failure

 ( ) F

 

DESCRIPTION: 

for the failure of the power electronic circuit or desconection of the pump.

the device has a protection system 

SYSTEM RESPONSE: If the devie doesn’t detect consumption of the electropump, this will be turned off and the system will work only with the 
other pump and its inverter. On the menu will appear NOM CURRENT P1 OFF (A16) NOM CURRENT P2 OFF (A17).
SOLUTION: Check the pump connections or contact with the tecnic service.

-10-

Summary of Contents for Speedbox

Page 1: ...INSTALLATION AND OPERATING INSTRUCTIONS INSTRUCCIONES PARA LA INSTALACIÓN Y UTILIZACIÓN ISTRUZIONI D INSTALLAZIONE E USO INSTRUCTIONS POUR L INSTALLATION ET L EMPLOI EN ES SPEEDBOX DUO IT FR ...

Page 2: ...ACIONES Y GENERALIDADES El producto tiene una garantía de 2 años a partir de la fecha de fabricación del producto El fabricante no se hará responsable de la garantía del producto en caso de una instalación o manipulación inadecuada Lea atentamente este manual para realizar la instalación del producto No deseche el manual después de haber realizado las operaciones de instalación puede ser útil para...

Page 3: ...nso wird empfohlen einen thermomagnetischen Schutzschalter für 20 A zu benutzen Es wird außerdem empfohlen eine unabhängige elektrische Leitung zu benutzen um mögliche elektromagnetische Interferenzen die ungewünschte Störungen der Haushaltsgeräte der Installation verursachen könnten zu vermeiden ACHTUNG Vor dem Hantieren im Inneren des Geräts muss dieses immer vom Stromnetz abgeschlossen werden N...

Page 4: ...en PROGRAMM MENÜ Datenfeldes Dieses kann jederzeit verlassen werden indem auf MENÜ gedrückt wird 3 6 Led Anzeigen LINE grün Stromspeisung Diese Anzeige leuchtet auf wenn das Gerät an die Stromspeisung angeschlossen wird FAILURE rot Je nach dem aufgetretenen Fehler blinkt diese Anzeige oder leuchtet kontinuierlich PUMP gelb Diese Anzeige leuchtet wenn die Pumpe in Betrieb ist und schaltet sich bei ...

Page 5: ...rzypadku zbiornika hydroforowego minimalna pojemnosc powinna wynosic 5L C It must be installed a pressure transmitter y otput 4 20 mA with pressure range either 0 10 bar or 0 16 bar 0 25 bar Installare un trasmettitore di pressione y uscita 4 20 mA e intervallo di pressione 0 10 bar o 0 16 bar installer un transmetteur de pression y avec 4 20 mA et la gamme de pression 0 10 bar ou 0 16 bar Se inst...

Page 6: ...mpa 2 Connection pompe 2 Conexión de la bomba 2 Verbindung zur Pumpe 2 Pompaansluiting 2 Podłączenie pompy 2 Power supply Alimentation générale Alimentazione elettrica Alimentación general Netzanschluss Voeding Zasilanie MT MM Fig 3 Pressure transmitter Trasduttore di pression Capteur de pression Transductor de presión Drucksensor Przetwornik ciśnienia External level probe Sonda di livello esterno...

Page 7: ...phase motor connection Collegamento motor a tre fasi Connexion motor triphasée Conexión motor trifásico 3 Phasen Motoranschluss Driefasige motoraansluiting Połączenie silnika trójfazowego U V W 3 230 V M U V 1 230 V M Fig 4 6 Single phase motor connection DISCONNECT BLACK CABLE Collegamento motor monofase SCOLLEGARE IL CAVO NERO Connexion motor monophasée DÉBRANCHEZ LE CÂBLE NOIR Conexión motor mo...

Page 8: ...m against over current the tries to connect the pump with a programmed periodicity because the water supply could have been ART restored n Automatic restore system after an interruption of power supply System is activated in AUTOMATIC mode keeping the configuration parameters see CONFIGURATION chapter n STC function Smart Temperature Control When the temperature of the electronic board reaches 85º...

Page 9: ...bling and pressure transmitter cabling The power cord can be replaced only by the manufacturer or his accredited representative Y Then the cabling is exposed as would be done to address any eventuality n Use cables type H07RN F with section enough to the power installed 2 n Power supply s 4 mm 2 n Motor supply s 1 mm If is necessary to increase the cable length outer joint is performed following t...

Page 10: ...ing the pq thermal protection This value is located over the characteristics plate of the motor Press ENTER for validation Using the pushbutton verify the rotation sense of pump 1 By mean of key 0 1 we p p can change it Press ENTER for validation Using the pushbutton verify the rotation sense of pump 2 By mean of key 0 1 we p p can change it Press ENTER for validation Using the keys q we can modif...

Page 11: ...the system is interrupted until the state of the level SOLUTION Check conections and or configuration of the extern exit as function LEVEL A5 TRANSDUCER Final failure DESCRIPTION the transducer damages are showed in the LCD screen SYSTEM REACTION the device operation is interrupted SOLUTION check the external pressure transmitter A6 EXCESSIVE TEMP PUMP 1 A7 EXCESSIVE TEMP PUMP 2 Final failure DESC...

Page 12: ...s in pump 2 n STARTS COUNT P1 Sows the number of starts of pump 1 n STARTS COUNT P2 Shows the number of starts of pump 2 n ON TIME P1 Shows the operating time of the pump 1 in hours n ON TIME P2 Shows the operating time of the pump 2 in hours n TIME INVERTER Shows the operating time of the inverter in hours n MAINS COUNTER Shows the number of connections to the electric supply M E N U E X P E R T ...