By mean of keys
input the nominal intensity value in A of pump 2 enabling the
pq
thermal protection. This value is located over the characteristics plate of the motor. Press
ENTER
for validation.
S E T
P O I N T
1 . 0
B a r
N O M .
C U R R E N T
P 1
5 . 0
A m p
N O M .
C U R R E N T
P 2
5 . 0
A m p
R O T .
S E N S E
P U M P 1
P U S H ↑ / C H E C K
0
R O T .
S E N S E
P U M P 2
P U S H ↑ / C H E C K
0
M I N .
F R E Q U E N C Y
1 8 . 0
H z
D I F .
S T A R T
P 1
0 . 5
B a r
D I F .
S T A R T
P 2
0 . 5
B a r
A L T E R N A T I O N
T
I M E
0 1
H O U R
D I G I T A L
I N P U T
N O
M I N .
P R E S S
A
L A R M
0 . 0
B a r
P R E S S U R E
S
E N S O R
0 - 1 0
B a r
The switching of the main pump (inverter) occur every cycle. In case of long periods of
operation, this value will switch the main pump after the time set.
Configuration of the minimum pressure in the system. With the value 0,0
bar, the control is disabled. If the system detects a pressure bellow the
“
MIN.PRES
” during a time longer than “
t.P.Min
” alarm A13 will appear.
The range of lecture of the pressure transmitter installed must be adjusted.
If the range is within 0-10 bar confirm by mean of
ENTER.
If the range is within 0-16 or 0-25 bar change it by mean of
pq
and then
confirm with
ENTER.
.
The default value is 0,5 bar. This value of pressure is the one that the system will
subtract to the input pressure, resulting the final pressure to which the system will set in
motion when the hydraulic network has a demand. Using keys pq to modify the initial
value. It is recommended
to maintain this value between 0,3 and 0,6 bar. Example:
- Input pressure: 2 bar.
- Differential start: 0,3 bar.
- Final start pressure: 2 - 0,3 = 1,7 bar.
The value should be greater as much as smaller be the accumulation and vice versa.
This will be the system operating pressure. Use keys
for modify the initial value (1 bar).
pq
WARNING
! The input pressure must be al least 1 bar lower than the maximum
pressure of the pumps.
By mean of keys
input the nominal intensity value in A of pump 1 enabling the
pq
thermal protection. This value is located over the characteristics plate of the motor. Press
ENTER
for validation.
Using the
pushbutton verify the rotation sense of pump 1. By mean of key
(0/1) we
p
p
can change it. Press
ENTER
for validation.
Using the
pushbutton verify the rotation sense of pump 2. By mean of key
(0/1) we
p
p
can change it. Press
ENTER
for validation.
Using the keys ▲
q
we can modify the minimum frequency value.
*The minimum frequency value will be used as a stop frequency in those installations
where the automatic detection of stoppage of the device does not act due to leaks in the
installation. See hydraulic installation.
Configuration of the time that the system can be working under the minimum
pressure before the minimum pressure alarm appears.
Use keys
pq
to select the external input type:
NO:
Disabled
LEVEL:
Enabled as external level control.
ON/OFF:
Closed contact -> System enabled / Opened contact -> System disabled
Second Pressure:
Closed contact -> Principal pressure / Opened contact -> Second
pressure enabled
START UP
n
Be sure that the pump is correctly primed
n
Connect the device to the electric supply with the magnetothermic switch, FAILURE led light will be ON. Wait for 10 seconds
while the device is doing the autotest. Once it finishes, led light FAILURE is OFF and led light LINE is ON. The LCD screen will
show message “SPEEDBOX DUO ” and inmediately the language display of the configuration mode.
n
The device is ready for being configured.
CONFIGURATION.
Using
pq
we can change the values and press
ENTER
for validation. Whenever we want to quit the
configuration sequence press
MENU
. After every
ENTER
it will appears automatically the different screens that constitute the configuration
sequence.
M E N U
L A N G U A G E
Hold
MENU
3 seconds.
By mean of keys
we can choose the languages: “LANGUAGE ENGLISH”,
pq
“LANGUE FRANÇAISE”, “LINGUA ITALIANA” and “IDIOMA ESPAÑOL”.
-9-
S E T
P O I N T
2
4 , 5 B a r
When
Second Pressure
is selected, the system can work in two different pressures
“
”
depending on the contact (opened or closed). The principal pressure is configured as
SET POINT
and the second pressure is configured as
SET POINT 2.
T I M E
M I N
P R E S
S
.
X X
s e c