34 WSA-XEE
122-402
M02S40N16-00
7.10 Display the status
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Main menu
Select
Machine State
3
Select
General, circuit, ecc..
4
Exit
7.11 General stata and central module
code
description
detailed description
AI-687
T.IN H2OUtil_B1
Inlet water temperature utility side
AI-687
T.OUT H2OUtil_B2
Outlet water temperature user side
AI-687
Ext.Air temp_B3
Outdoor air temperature
AI-687
S.DemandLimit_X1
Signal of the demand limit function controls
AI-687
S.WaterReset_X2
Signal of the water reset function controls
AI-687
RHExt_X3
Outside relative humidity
AI-687
El.CabinetTemp_X4
Electrical panel temperature
AO-687
%FREE-COOLING _X5
Percentage value of the status of the external control signal of the ventilation/FREE-COOLING valve
DI-687
Sel.SetPoint_DU2
Status of the second digital input setpoint 0=1°set 1=2°Set
DI-687
SystemPressure_DU1
Status of the system water pressure sensor 0=OK 1=Fault
DI-687
FlowUser_X8
Status of the differential pressure switch/utilisation flow 0=OK 1=Fault
DI-687
ON-OFFRem_X7
Status of the unit status digital input 0=OFF 1=On
DI-687
Heat/CoolRem_X6
Status of the unit mode digital input 0=Heat 1=Cool
DI-687
PhaseMonitor_DL1
Status of the phase monitor input 0=OK 1=Fault
DI-687
OvlP1Util_D2
Status of thermal protection contact of utilisation pump 1 0=OK 1=Fault
DI-687
OvlP2Util_D1
Status of thermal protection contact of utilisation pump 2 0=OK 1=Fault
DI-687
OvlP3Util_DL2
Status of thermal protection contact of utilisation pump 3 0=OK 1=Fault
DO-687
El.CabinetFAN_DO1
Status of the ventilation control of the electrical panel: 0=Off 1=On
DO-687
El.CabinetHEAT_DO2
Status of the heating control of the electrical panel: 0=Off 1=On
DO-687
UnitMode_Q1
Status of the digital output related to the operating mode (N.O. Open=Cool N.O. Closed=Heat): 0=Cool 1=Heat
DO-687
Cumul.Alarm_Q2
Unit cumulative alarm status (N.0.Open=All OFF N.O. Closed=All ON): 0=Off 1=On
DO-687
CmdP1User_Q3
Command pump 1 utility side: 0=Off 1=On
DO-687
CmdP2User_Q4
Command pump 2 utility side: 0=Off 1=On
DO-687
CmdP3User_Q5
Command pump 3 utility side: 0=Off 1=On
DO-687
OpenYV FC_Q7
Opening control of the FREE-COOLING valve FC Closed = ON: 0=Off 1=On
DO-687
CloseYV FC_Q8
Closure control of the FREE-COOLING valve FC Closed = OFF: 0=Off 1=On
DO-687
AntifreezeHeater_Q6
Status of the control of the antifreeze heaters: 0=Off 1=On
S0001
StartsP1User
Number of startup totalized from Pump 1
S0002
StartsP2User
Number of startup totalized from Pump 2
S0003
StartsP3User
Number of startup totalized from Pump 3
S0004
Pump1 running hours Utilisation pump 1 hours
S0005
Pump2 running hours Utilisation pump 2 hours
S0006
Pump3 running hours Utilisation pump 3 hours
S0007
Antifreeze heat.
Antifreeze heater status 0=Off 1=On
S0008
Pump in antifreeze
Status of the utilisation pump for antifreeze protection 0=Off 1=On
S0009
Recovery
Recovery status: 0=Off 1=On
S0010
ActualSptTExt
Setpoint value calculated by the Text climate curve
S0011
ActualSptWR
Setpoint value calculated by the WaterReset function
S0012
StatusFREE-COOLING
FREE-COOLING status 0=Off 1=On
S0013
GenWarning
0=Off 1=On
S0014
GenBlock
0=Off 1=On
S0015
NCompOnUnit
Number of compressors currently active on the machine
Summary of Contents for WSA-XEE 182
Page 8: ...8 WSA XEE 122 402 M02S40N16 00 2 4 Removable fan section for shipping...
Page 15: ...M02S40N16 00 WSA XEE 122 402 15 5 6 Connections performer by customer Q 6...
Page 58: ...58 WSA XEE 122 402 M02S40N16 00 Page intentionally left blank...
Page 59: ...M02S40N16 00 WSA XEE 122 402 59 Page intentionally left blank...