Sound levels
Size
Sound
power
level
Sound
pressure
level
Sound power level (dB)
Octave band (Hz)
63
125
250
500
1000
2000
4000
8000
dB(A)
dB(A)
122
69
74
76
75
70
65
62
52
76
59
162
70
75
77
76
71
67
64
52
77
60
182
74
78
81
79
74
70
66
55
80
63
222
75
79
82
80
75
72
67
56
81
64
262
71
76
79
77
73
70
65
56
79
61
302
76
81
83
81
77
73
68
58
82
65
352
77
82
85
82
78
76
70
58
84
66
402
80
86
88
85
81
79
73
62
87
70
Sound levels refer to units at full load.
The sound pressure is measured at 1 m from the external surface of the ducted unit operating in an open field. (standard UNI EN ISO 9614-2)
Data referred to the following conditions:
- Internal exchanger water temperature = 12/7°C
- outdoor air temperature 35°C
- Static available pressure 120 Pa
Please note that when the unit is installed in conditions different from nominal test conditions (e.g. near walls or obstacles in general), the sound levels may undergo substantial variations.
Operating range
Size
122
162
182
222
262
302
352
402
External exchanger
Max entering air temperature
1
°C
45
45
45
45
45
45
45
44
Max entering air temperature
2
°C
48
48
48
48
48
48
48
47
Min. entering air temperature
3
°C
-10
-10
-10
-10
-10
-10
-10
-10
Min. entering air temperature
4
°C
-7.0
-7.0
-7.0
-7.0
-7.0
-7.0
-7.0
-7.0
Internal exchanger
Max inlet water temperature
°C
21
27
27
27
27
27
24
24
Min. leaving water temperature
5
°C
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
Min. leaving water temperature
6
°C
-7.0
-7.0
-7.0
-7.0
-7.0
-7.0
-7.0
-7.0
Data referred to the following conditions:
Internal exchanger water temperature = 12/7°C
Entering eExternal exchanger air temperature = 35°C
1. unit at full load
2. Unit with automatic staging of the compressor capacity.
3. unit at full load
4. Part-load unit
5. Standard unit and external exchanger entering air 35 °C (no ‘Low water temperature (Brine)’ configuration).
6. Unit in ‘Low water temperature (Brine)’ configuration. Fluid processed with 40% ethylene glycol
Graph referred to size 352
The detail of each size is shown in tabular date.
Ta (°C) = entering external exchanger air temperature (dry bulb).
To (°C)= leaving internal exchanger water temperature
1. Standard unit:(no “Liquid low temperature” configuration)
2. Operation field extension for unit in ‘Low water temperature
(Brine)’ configuration (40% ethylene glycol).
3. Unit with automatic staging of the compressor capacity.
4. Unit at full-load with air flow automatic modulation
Summary of Contents for WSA-XEE 182
Page 8: ...8 WSA XEE 122 402 M02S40N16 00 2 4 Removable fan section for shipping...
Page 15: ...M02S40N16 00 WSA XEE 122 402 15 5 6 Connections performer by customer Q 6...
Page 58: ...58 WSA XEE 122 402 M02S40N16 00 Page intentionally left blank...
Page 59: ...M02S40N16 00 WSA XEE 122 402 59 Page intentionally left blank...