If there are more units connected in a local network set the mode of operation.
MODE A
Every unit manages its own compressors according to the
setpoint.
Every unit optimizes its refrigeration circuits.
Pumps always active, even with compressor stoped.
P0343 = 0
P0344 > 0 °C
setpoint1 > setpoint2 > setpoint3
or
setpoint1 < setpoint2 < setpoint3
MODE B
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Pumps always active, even with compressor stoped.
P0343 = 1
P0344 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: optimal H2O temperature control
MODE C
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Active pumps only with active compressors.
P0343 = 2
P0344 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: minimum pumps consumption need balanced system (t1 = t2 = t3)
Path: Main Menu / Unit parameters / Master Slave
Parameters
Short description
Description
P0340:
Address unit
ProcessBus address unit
P0341:
Unit network
Number of network-connected units including the master
P0342:
Standby unit
Number of units kept in standby
P0343:
TypeRegMS
Operation mode: 0=mode A; 1=mode B; 2=mode C
P0344:
Offset Trm MS
Temperature Offset the master sum or subtract, depending on the way you set, in order of priority, to the set point of
the slave
Summary of Contents for WSA-XEE 182
Page 8: ...8 WSA XEE 122 402 M02S40N16 00 2 4 Removable fan section for shipping...
Page 15: ...M02S40N16 00 WSA XEE 122 402 15 5 6 Connections performer by customer Q 6...
Page 58: ...58 WSA XEE 122 402 M02S40N16 00 Page intentionally left blank...
Page 59: ...M02S40N16 00 WSA XEE 122 402 59 Page intentionally left blank...