M02S40N16-00
WSA-XEE
122-402
33
code
detailed description
t.i.
module
input
t.a.
ee126:
Faulty probe - source 2 temperature
AI
985 circuit 1
T2 X1
A
ee127:
Faulty probe - Suction temperature
AI
94U driver
T2 X2
A
ee128:
Faulty probe - discharge pressure
AI
985 circuit 1
T2 X3
A
ee129:
Faulty probe - suction pressure
AI
94U driver
T1 X1
A
ee130:
Faulty probe - Recovery gas temperature
AI
965 recovery
T1 X1
A
ee131:
Faulty probe - Recovery pressure
AI
965 recovery
T2 X7
A
ee132:
Faulty probe - Water recovery inlet
AI
965 recovery
T1 X2
A
ee133:
Faulty probe - Water recovery outlet
AI
965 recovery
T1 X3
A
ee135:
Bios wrong version
985 circuit 1
A
ff105:
Low overheating Thermostatic C1
A
fF109:
Low pressure from analogic input
DI
985 circuit 1
T3 X7
A/M
ff110:
Pre-alarm - low pressure COOL mode
A
ff111:
Pre-alarm - low pressure HEAT mode
A
fF112:
Low pressure from analogic input
AI
94U driver
T1 X1
A/M
fF113:
High pressure from digital input
DI
985 circuit 1
T3 X8
A/M
ff114:
Pre-alarm - high pressure
A
fF115:
High pressure from analogic input
AI
985 circuit 1
T2 X3
A/M
ff116:
Pre-alarm max. compression ratio (high pressure / low pressure)
A
fF117:
Min. compression ratio (high pressure / low pressure)
A/M
FF119:
Alarm max. compression ratio (high pressure / low pressure)
M
FF134
Empty circuit
AI
94U driver
T1 X1
M
ff136:
Defrost: low gas temperature
Logico
985
X2
M
fF137:
Oil pressure
DI
985
DL1
A/M
ff138:
Low condensing pressure
Logico
985
X3
A
fF139:
Maximum saturated condensation temperature
Logico
A/M
fF140:
Minimum saturated condensation temperature
Logico
A/M
fF141:
Maximum saturated evaporation temperatur
Logico
A/M
fF142:
Minimum saturated evaporation temperatur
Logico
A/M
fF143:
Maximum compression ratio
Logico
A/M
FF144:
Minimum compression ratio
Logico
M
fF145:
Maximum engine torque
Logico
A/M
iI002:
Low water pressure
DI
687 central
T5 DU1
A/M
iI006:
Flow switch utility side
DI
687 central
T3 X8
A/M
II007:
Freeze alarm utility side
M
ii008:
Utility side pumps On for antifreeze alarm
A
II009:
COOL:
outlet temperature higher than inlet temperature
HEAT:
inlet temperature higher than outlet temperature
A
iI120:
Flow switch source side
DI
985 circuit 1
T2 X4
A/M
II121:
Freeze alarm source side
A
II042:
FCI module, system pressure
DI
955 FCI
X3
M
II043:
FCI module, antifreeze alarm
Logico
955 FCI
X1
M
ii047:
FCI module, water flow alarm
DI
955 FCI
X4
A
ii052:
Recosery module, flow alarm
DI
965 REC
X6
A
ii053:
Recovery module, system pressure
DI
965 REC
X6
A
Summary of Contents for WSA-XEE 182
Page 8: ...8 WSA XEE 122 402 M02S40N16 00 2 4 Removable fan section for shipping...
Page 15: ...M02S40N16 00 WSA XEE 122 402 15 5 6 Connections performer by customer Q 6...
Page 58: ...58 WSA XEE 122 402 M02S40N16 00 Page intentionally left blank...
Page 59: ...M02S40N16 00 WSA XEE 122 402 59 Page intentionally left blank...