54 WSA-XEE
122-402
M02S40N16-00
Admissible water flow rates
Min. (Qmin) and max. (Qmax) water flow-rates admissibles for the correct unit operation
Size
122
162
182
222
262
302
352
402
Qmin
[l/s]
1.0
1.1
1.3
1.5
1.7
2.9
3.2
3.6
Qmax
[l/s]
2.8
3.2
3.6
4.2
4.7
8.1
9.0
10.2
Exchanger operating range
TYPE OF TEST
Internal exchanger
DPr
DPw
[kPa]
[kPa]
CLIVET C
4500
1000
PED (CE)
4500
1000
DPr = Max. operating pressure referigerant gas side
DPw = Max. operating pressure water side (utility)
Overload and control device calibrations
Setting instruments
apre
chiude
valore
High pressure safety pressure switch
[kPa]
4050
3300
-
Low pressure safety switch
[kPa]
450
600
-
low pressure switch (Brine)
[kPa]
200
350
-
antifreeze protection
[°C]
3
5.5
-
high pressure safety valve
[kPa]
-
-
4500
low pressure safety valve
[kPa]
-
-
3000
Max no. of compressor starts per hour
[n°]
-
-
10
high compressor discharge temperature safety thermostat
[°C]
-
-
120