code
description
detailed description
DO-965
YV1Rec_DO1
Command valve YV1 0=Off 1=On
DO-965
YV2Rec_DO2
Command valve YV2 0=Off 1=On
DO-965
YV3Rec_Q1
Command valve YV3 0=Off 1=On
DO-965
YV4Rec_Q2
Command valve YV4 0=Off 1=On
DO-965
YV5Rec_Q3
Command valve YV5 0=Off 1=On
DO-965
PmpRec_Q4
Recovery pump command 0=Off 1=On
7.15 Master slave status
code
description
detailed description
S0600
SetPoint Unit1
Value accessible from the display of the unit machine network master.
Working setpoint master unit (Address 1 on periferalbus)
S0601
SetPoint Unit2
Value accessible from the display of the unit machine network master.
Working setpoint unit 2 (Address 2 on periferalbus)
S0602
SetPoint Unit3
Value accessible from the display of the unit machine network master.
Working setpoint unit 3 (Address 3 on periferalbus)
S0603
SetPoint Unit4
Value accessible from the display of the unit machine network master.
Working setpoint unit 4 (Address 4 on periferalbus)
S0604
SetPoint Unit5
Value accessible from the display of the unit machine network master.
Working setpoint unit 5 (Address 5 on periferalbus)
S0605
SetPoint Unit6
Value accessible from the display of the unit machine network master.
Working setpoint unit 6 (Address 6 on periferalbus)
S0606
SetPoint Unit7
Value accessible from the display of the unit machine network master.
Working setpoint unit 7 (Address 7 on periferalbus)
S0607
statusUnit1
Value accessible from the display of the unit machine network master.
Status master unit 7 0=Off 1=Eco 2=On 3=PmpOn
S0608
StatusUnit2
Value accessible from the display of the unit machine network master.
Status unit 2 0=Off 1=Eco 2=On 3=PmpOn
S0609
StatusUnit3
Value accessible from the display of the unit machine network master.
Status unit 3 0=Off 1=Eco 2=On 3=PmpOn
S0610
StatusUnit4
Value accessible from the display of the unit machine network master.
Status unit 4 0=Off 1=Eco 2=On 3=PmpOn
S0611
StatusUnit5
Value accessible from the display of the unit machine network master.
Status unit 5 0=Off 1=Eco 2=On 3=PmpOn
S0612
StatusUnit6
Value accessible from the display of the unit machine network master.
Status unit 6 0=Off 1=Eco 2=On 3=PmpOn
S0613
StatusUnit7
Value accessible from the display of the unit machine network master.
Status unit 7 0=Off 1=Eco 2=On 3=PmpOn
7.16 Hydronic module status
code
description
detailed description
AO-965
%CmdInverter_X7
% value inverter command signal
DI-965
OvlP1.Hid_X4
Pump 1 overload 1: 0=OK 1=Fault
DI-965
OvlP2.Hid_X5
Pump 2 overload: 0=OK 1=Fault
DI-965
OvlP3.Hid_X6
Pump 3 overload: 0=OK 1=Fault
DI-965
OvlInv.Hid_DL1
Inverter overload: 0=OK 1=Fault
DO-965
CmdP1.Hid_DO1
Pump 1 command: 0=Off 1=On
DO-965
CmdP1Inv.Hid_Q2
Pump 1 inverter command: 0=Off 1=On
DO-965
CmdP2.Hid_DO2
Pump 2 command: 0=Off 1=On
DO-965
CmdP2Inv.Hid_Q3
Pump 2 inverter command: 0=Off 1=On
DO-965
CmdP3.Hid_Q1
Pump 3 command: 0=Off 1=On
DO-965
ComdP3Inv.Hid_Q4
Pump 3 inverter command: 0=Off 1=On
DO-965
CmdInverter:X8
Hydronic inverter command: 0=Off 1=On
S0500
StartsP1Hidro
Hydronic module pump 1 starts
S0501
StartsP2Hidro
Hydronic module pump 2 starts
S0502
StartsP3Hidro
Hydronic module pump 3 starts
S0503
HoursP1.Hid
Hydronic module pump 1 hours
S0504
HoursP32.Hid
Hydronic module pump 2 hours
Summary of Contents for WSA-XEE 182
Page 8: ...8 WSA XEE 122 402 M02S40N16 00 2 4 Removable fan section for shipping...
Page 15: ...M02S40N16 00 WSA XEE 122 402 15 5 6 Connections performer by customer Q 6...
Page 58: ...58 WSA XEE 122 402 M02S40N16 00 Page intentionally left blank...
Page 59: ...M02S40N16 00 WSA XEE 122 402 59 Page intentionally left blank...