7.9 Alarms
Before resetting an alarm identify and remove its cause.
Repeated resets can cause irreversible damage.
Example:
+ eE001: Monitore fase: Fault = active alarm
- EE003: Guasto P1 Util: Ok = resetted alarm
Display of alarm: step 1-3
Reset allarm: step 4-10
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Alarm list detail
Press
3
Alarm list
Select
Alarm
4
Alarm list detail
Press 3 sec.
5
Password
Set
Enter password
6
Alarm list detail
Press
7
Alarm list
Select
Alarm
8
Select
Reset
Executed
9
Press 3 sec.
10
Password management
Select
Log off
The alarm code identifies the concerned circuit:
Example:
ee 1 01:TimeOutModCirc = circuit 1
ee 2 01:TimeOutModCirc = circuit 2
The number of refrigerant circuits depends on series and size of the unit.
t.i. input type:
DI = digital input
AI = analogic input
Module:
687 = main module
985 = circuit module
94U = thermostatic driver module
Input:
Connector number:
T1, T2, T3.....
PIN code:
X1, X2, Q13, DO1.....
t.a. alarm type:
A automatic reset
M manual reset
A/M automatic reset, (after N alarm interventions becomes manual reset)