55
Statia- tab 1
MENU
ID
Short description
Description
1 Main Page
-
Machine status
Current unit status [0]:Off, [1]:ECO, [2]:ON, [3]:FAN
1 Main Page
-
Machine mode
Current unit mode [0]:COOL, [1]:HEAT
1 Main Page
-
Current setpoint
Current unit setpoint
1 Main Page
-
No. of steps used
Number of compressors currently activated
10 Main Index
-
Clean
Clean control from HMI
3001 Central POL687 - IO
-
IntakeTemp._B1:AI-687
Return temperature detected by the main board's analogue input
3001 Central POL687 - IO
-
OutdoorTemp._B3:AI-687
Outside temperature
3001 Central POL687 - IO
-
SupplyTemp._B2:AI-687
Supply temperature
3001 Central POL687 - IO
-
%Cmd RicicDamper_X1:AO-687
Recirculation damper opening control percentage
3001 Central POL687 - IO
-
QualityAir_X2:AI-687
Air quality value from analogical input
3001 Central POL687 - IO
-
SupplyPDiff_X3:AI-687
Supply fan differential pressure to calculate air flow rate
3001 Central POL687 - IO
-
ExternalPDiff_X4:AI-687
Return external differential pressure to examine pressure drops on the
return channel and, if necessary, adjust the external damper
3001 Central POL687 - IO
-
ON-OFFRem_DU1:DI-687
On/off digital input status (open OFF, closed ON)
3001 Central POL687 - IO
-
Heat/CoolRem_DU2:DI-687
Digital input status for mode change (open COOL, closed HEAT)
3001 Central POL687 - IO
-
PhaseControl_D1:DI-687
Phase monitor alarm input status (open ALARM)
3001 Central POL687 - IO
-
Ovl SupplyFan_DL1:DI-687
Supply fan thermal digital input status (open ALARM)
3001 Central POL687 - IO
-
Ovl RipEspFan_DL2:DI-687
Return/exhaust fan thermal digital input status (open ALARM)
3001 Central POL687 - IO
-
Diff. Filters_D2:DI-687
Supply air filters differential input status (open INSUFFICIENT FLOW)
3001 Central POL687 - IO
-
Fire Alarm_X8:DI-687
Fire alarm input status (open ALARM)
3001 Central POL687 - IO
-
%Cmd Supply Fan_X5:AO-687
Modulating supply fan control percentage
3001 Central POL687 - IO
-
%Cmd ExternalDamper_X7:AO-687
External damper opening control percentage
3001 Central POL687 - IO
-
%Cmd EjectionDamper_X6:AO-687
Exhaust damper opening control percentage
3001 Central POL687 - IO
-
Cmd CumAlarm_Q2:DO-687
Alarm cumulative control status
3001 Central POL687 - IO
-
Cmd EjectionDamper_Q5:DO-687
Exhaust damper/fan control status
3001 Central POL687 - IO
-
Cmd Humidifier_Q6:DO-687
Humidifier control status
3001 Central POL687 - IO
-
Cmd SupplyFan_Q3:DO-687
Supply fan control status
3001 Central POL687 - IO
-
Cmd ReturnFan_Q4:DO-687
Return fan control status
3001 Central POL687 - IO
-
Cmd ModeUnit_Q1:DO-687
Unit mode control status (open COOL, closed HEAT)
3001 Central POL687 - IO
-
AntifreezeHeater_Q8
Control status of the antifreeze heaters for source side water exchang-
ers
3002 Expansion POL955 - IO
-
ReturnPDiff_X4:AI-955
Return fan differential pressure to calculate air flow rate
3002 Expansion POL955 - IO
-
Freeze Addition_X3:AI-955
Water coil output temperature for additions' antifreeze function
3002 Expansion POL955 - IO
-
RH% outdoor_X2:AI-955
Outside relative humidity value
3002 Expansion POL955 - IO
-
Supply Pressure_X5:AI-955
Absolute pressure status on supply channel
3002 Expansion POL955 - IO
-
RH% Return_X1:AI-955
Relative return humidity value
3002 Expansion POL955 - IO
-
HT Addition_X6:DI-955
Additions' high temperature alarm input status
3002 Expansion POL955 - IO
-
Ovl Addition_X7:DI-955
Addition protections alarm input status
3002 Expansion POL955 - IO
-
Supply Flux_X8:DI-955
Supply air flow switch status
3002 Expansion POL955 - IO
-
%Cmd Addition_Y2:AO-955
Integration element control percentage
3002 Expansion POL955 - IO
-
%Cmd Return Fan_Y1:AO-955
Return fan control percentage
3002 Expansion POL955 - IO
-
Cmd Addition Pump_Q1:DO-955
Additions' pump control for water coil
3002 Expansion POL955 - IO
-
Cmd Addition 1_Q2:DO-955
Addition 1 control
Summary of Contents for CSRN-XHE2 Series
Page 1: ...CSRN XHE2 49 4 110 4 R 410A M07V40B13 07 11 20 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Page 75: ...Dimensional drawings 75...
Page 77: ...Dimensional drawings 77...
Page 79: ...Dimensional drawings 79...
Page 81: ...Dimensional drawings 81...
Page 83: ...Dimensional drawings 83...
Page 85: ...Dimensional drawings 85...
Page 87: ...Dimensional drawings 87...
Page 89: ...Dimensional drawings 89...
Page 91: ...Dimensional drawings 91...