27
BACNET LONWORK
LED BSP
communication with AP1 module
green
communication
ok
yellow
software ok but communication with AP1
down
red
flashing : software error
fixed : hardware error
LED BUS
communication with BACNET
green
ready for communication
yellow
startup
red
BACnet server down
restart after 3 sec.
LED BSP
communication with AP1 module
green
communication
ok
yellow
software ok but communication with AP1
down
red
flashing : software error
fixed : hardware error
LED BUS
communication with LONWORK
green
communication
ok
yellow
startup
flashing: communicating not possible
red
communication
down
LONWORK CABLE TYPES
Echelon allows three cable types for channel type TP/FT-10,
including the
Category 5 network cable used commonly in building
automation and control (TIA
568A Cat-5).
CAT-5 SPECIFICATIONS
Unshielded cable, twisted pair with at least 18 beats per
meter:
Cross-sectional area Min. 0.5mm, AWG24, 0.22mm²
Impedance 100
Ω
+/- 15 % @ f > 1 MHz
Operating capacity between two wires of a pair < 46 nF/km
Capacity pair to ground, asymmetric. < 3.3 nF/km
DC loop resistance < 168
Ω
Summary of Contents for CSRN-XHE2 Series
Page 1: ...CSRN XHE2 49 4 110 4 R 410A M07V40B13 07 11 20 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Page 75: ...Dimensional drawings 75...
Page 77: ...Dimensional drawings 77...
Page 79: ...Dimensional drawings 79...
Page 81: ...Dimensional drawings 81...
Page 83: ...Dimensional drawings 83...
Page 85: ...Dimensional drawings 85...
Page 87: ...Dimensional drawings 87...
Page 89: ...Dimensional drawings 89...
Page 91: ...Dimensional drawings 91...