Immersed electrode humidifier
Option
Connexion humidificateur: 1” F
Supply water
The humidifier must be supplied with mains water having the following features:
pressure between 0.1 and 0.8 Mpa (1 – 8 bar)
temperature between 1 and 40°C
Do not use:
water treated with softeners: it can corrode the electrodes and form foam with possible faults/
malfunctionings
pit, industrial or potentially polluted (chemically or bacteriologically) water
disinfectants or anti-corrosive substances mixed with water, as potentially irritating
Supplying the humidifier with water treated with reverse osmosis filtering system gives the following
advantages:
reduces limescale deposits
reduces energy consumptions
reduces maintenance costs
increases humidifier duration
Check that the filter guarantees a water flow rate higher than the flow rate of the installed humidifier.
Limit values for the supply water
Respect the limits indicated in the table
No relation can be demonstrated between water hardness and conductivity.
Limit values for the supply
water
conductivity
medium-low
medium-high
min max min max
Hydrogen
ions
pH
7 8,5 7 8,5
Specific conductivity at 20°C
μ
S/cm 125
500
300
1250
Total dissolved solids
TDS
mg/l
(1) (1)
(1) (1)
Dry residue at 180°C
R
180
mg/l
(1)
(1)
(1)
(1)
Total hardness
TH
mg/l CaCO
3
50
(2)
250 100
(2)
400
Temporary hardness
mg/l CaCO
3
30
(3)
150 60
(3)
300
Iron + Manganese
mg/l Fe+Mn
0
0,2
0
0,2
Chlorides
ppm
Cl 0 20 0 30
Silica
mg/l SIO
2
0 20 0 20
Residual chlorine
mg/l Cl
-
0 0,2 0 0,2
Calcium sulphate
mg/l CaSO
4
0 60 0 100
Metallic impurities
mg/l 0 0 0 0
Solvents, diluents, soaps,
lubricants
mg/l 0 0 0 0
(2) not lower than 200% of the chloride
content in mg/l of Cl-
(3) not lower than 300% of the chloride
content in mg/l of Cl-
(1) Values depending on specific conductivity;
in general:
Drainage water
It can reach a temperature of 100°C.
It contains the same substances of the supply water but in higher concentration.
As it is not toxic, it can be disposed of with white waters.
Summary of Contents for CSRN-XHE2 Series
Page 1: ...CSRN XHE2 49 4 110 4 R 410A M07V40B13 07 11 20 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Page 75: ...Dimensional drawings 75...
Page 77: ...Dimensional drawings 77...
Page 79: ...Dimensional drawings 79...
Page 81: ...Dimensional drawings 81...
Page 83: ...Dimensional drawings 83...
Page 85: ...Dimensional drawings 85...
Page 87: ...Dimensional drawings 87...
Page 89: ...Dimensional drawings 89...
Page 91: ...Dimensional drawings 91...