C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
50
Blower Performance Data – TSL18
Table 5k
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1" filter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%
RPM/Watt Tolerance 10%
External Static Pressure (in. wg)
PSC - High Static
Speed Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Low
RPM
1030
1090
1110
1120
1130
Power (W)
246
235
223
212
200
CFM
760
710
650
580
510
Medium
RPM
1130
1130
1140
1140
Power (W)
251
239
228
216
CFM
750
680
610
530
High
RPM
1180
1180
1170
Power (W)
Operation not recommended
282
270
258
CFM
740
660
570
ECM - Constant T
orque
Speed Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
RPM
750
800
850
880
Power (W)
73
77
82
87
Operation not recommended
CFM
590
550
500
450
2
RPM
820
860
910
960
990
1030
Power (W)
95
99
105
110
115
119
CFM
660
630
590
540
500
460
3
RPM
890
930
960
1040
1060
1090
1130
1200
Power (W)
123
127
132
138
144
149
154
158
CFM
730
700
670
640
590
550
520
490
4
RPM
970
1000
1080
1110
1140
1170
1220
Power (W)
148
152
158
164
170
176
172
CFM
750
720
690
660
610
570
520
5
RPM
1230
1180
1180
Power (W)
Operation not recommended
217
182
154
CFM
730
580
470
ECM - Constant V
olume
CFM
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
500
RPM
660
750
850
920
990
1060
1120
1200
Power (W)
52
67
81
96
110
125
139
153
600
RPM
760
840
920
1010
1070
1130
1200
1270
Power (W)
88
102
116
130
144
158
172
186
700
RPM
860
930
980
1090
1150
1210
1280
1340
Power (W)
138
153
167
182
196
211
225
240
800
RPM
960
1010
1050
1170
1220
1280
1360
1400
Power (W)
199
216
232
249
265
282
298
315