TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Typical Cabinet with “G” Installation – Recessed
Notes:
1.
The cabinet configuration will determine the slab core drilling location and the wall surrounding the cabinet.
2. Stud walls surrounding the cabinet are recommended. For better sound attenuation, the drywall studs should not be attached to or
contacting the cabinet.
3.
The “G” style return air panel overlaps its rough opening. Allow a minimum of 3.5” (89) of drywall to a corner. Do not caulk the return air
panel to the wall.
4.
The “G” panel attaches to the cross bars of the frame kit. The cabinet must be recessed behind the wall.
5.
For air filter access, pivot the hinged inner panel and open the snapped filter access panel.
6. For chassis access,
a. Remove the entire G-Panel
b. Remove the (2x) cross bars of the frame kit
c. Remove the cabinet’s filter panel
d. Slide out the chassis
7.
When untreated outside air will be utilized, the 48A0100N04 motorized damper must be used. The mixed air temperature must be no
lower than 45°F degrees (7°C), must be no higher than 95°F DB/75°F WB, and must not exceed 20% of the cabinets total CFM output.
8.
For a 2” filter, set the cabinet 6.25” (158) from the front of the dry wall.
9.
If the drywall flanges (Qty. 4) are removed, the cabinet can be set 1” (25) closer to the finished drywall.
10.
All dimensions are inches (mm) with all nominal 2” x 4” studs being 1.5” (38) x 3.5” (89).
G Style
Return Air Panel
6.00
(152)
Note 8, 9
DRYWALL
5/8"
(16)
CABINET
TOP VIEW
3-1/2
(89)
It is recommended to leave 2” (51) minimum clearance
on both sides for removing panel
X
Seal Gap (4) Sides
X
Frame
Outside
Drywall
C
57-1/2
(1460) R.O.
5-7/8*
(149)
Floor
12-1/4
(311)
28-5/8
(727)
(Order seperately)
Refer to the IOM packaged with the motorized
damper assembly for installation instructions and
note 7 (below) for its usage.
D
59
(1599)
4.50* (114)
Front View
Frame Installed
G Panel
Perimeter
4 Panel
Crossbars
Lowest Pair
of Tabs
Third Pair of
Tabs from Bottom
Mounting cage
Nuts (1/4-20)
* Dimension if cabinet is on floor.
Add if cabinet is on stand/pad.
R.O.
Frame
1
2
Cross Bar
1
2
Description
Kit Part Qty
B
A
Cabinet
Flange
1.25 (32)
Frame
Crossbars
(Note 4)
XX
FRONT VIEW
48A0100N51
48A0100N50
48A0100N52
19-5/8
(498)
16-5/8
(400)
19
(483)
17.00
(432)
24
(610)
19.25
(489)
17.00
(432)
24.25
(616)
24-3/8
(620)
15-18
09-12
24-36
Panel
C
B
A
Kit
Size
D
21.50
(546)
18.50
(470)
25.50
(648)
Frame Kit
�
NOTICE!
�
Recessed cabinet requires a frame kit.
Outside air applications require a Motorized
Damper or pre-treated air that is above 45ºF
degrees (7ºC) and below 95F degrees dry
bulb/75ºF degrees wet bulb.
Attach the frame to the wall studs, not the
cabinet. Use weather seal material between
the frame and cabinet to avoid bypass air being
pulled in from the wall cavity.
Do not distort frame. Shim the sides, if required.
Note 5
Optional Damper Motor
“G” Frame
9” x 2” (228 x 51)
Knockout outside air
opening left of right side
to suit installation
24.12 (612)
1
4.75 (120)