C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
40
Blower Performance Data – TSM09
Table 5a
External Static Pressure (in. wg)
PSC - Low Static
Speed Tap
0.0
0.1
0.2
0.3
Low
RPM
760
870
Power (W)
59
54
CFM
290
270
Medium
RPM
890
940
1000
Power (W)
71
66
61
CFM
350
310
270
High
RPM
990
1060
1080
1100
Power (W)
85
80
75
69
CFM
400
370
310
240
ECM - Constant T
orque
Speed Tap
0.0
0.1
0.2
0.3
1
RPM
680
Power (W)
20
CFM
250
2
RPM
760
870
Power (W)
27
30
CFM
290
270
3
RPM
930
1000
1100
1180
Power (W)
43
47
51
54
CFM
370
340
320
290
4
RPM
1010
1070
1160
1240
Power (W)
54
58
62
66
CFM
410
380
360
330
ECM - Constant
Volume
CFM
0.0
0.1
0.2
0.3
250
RPM
680
830
960
1120
Power (W)
22
30
38
47
300
RPM
780
920
1060
1200
Power (W)
29
38
48
58
350
RPM
890
1020
1160
1280
Power (W)
40
50
62
73
400
RPM
990
1110
1240
1340
Power (W)
52
65
79
92
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1” filter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.
Denotes Operation not recommended.