c l i m a t e m a s t e r.c o m
41
TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Blower Performance Data – TSM12
Table 5b
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1” filter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.
Denotes Operation not recommended.
External Static Pressure (in. wg)
PSC - Low Static
Speed Tap
0.0
0.1
0.2
0.3
Low
RPM
760
Power (W)
61
CFM
300
Medium
RPM
830
930
Power (W)
74
69
CFM
340
320
High
RPM
1030
1090
1120
Power (W)
90
85
79
CFM
450
420
360
ECM - Constant T
orque
Speed Tap
0.0
0.1
0.2
0.3
1
RPM
800
Power (W)
29
CFM
320
2
RPM
870
960
1050
Power (W)
40
44
48
CFM
360
340
310
3
RPM
960
1040
1130
1220
Power (W)
59
63
67
71
CFM
410
390
370
350
4
RPM
1030
1110
1190
1280
Power (W)
78
82
87
91
CFM
450
430
420
400
ECM - Constant V
olume
CFM
0.0
0.1
0.2
0.3
300
RPM
760
890
1040
1170
Power (W)
29
38
48
58
350
RPM
850
980
1100
1220
Power (W)
40
50
62
73
400
RPM
940
1060
1170
1280
Power (W)
52
65
79
92
450
RPM
1030
1140
1230
1330
Power (W)
73
87
101
115
500
RPM
1120
1220
Power (W)
97
111