C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
TSM/TSL Vertical Stack
R e v. : J a n u a r y 1 8 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
30
Drywall Openings
NOTICE - Drywall openings shown below are for specific
cabinets as indicated. Cut openings for your cabinet,
supply air grille, and thermostat.
Slab
88”
(2235)
(152)
(1461)
(2235)
57½”
6”
19
½
”
(495)
19.25”
(489)
Slab
Opening 12” x 12”
For Supply Air Grille
A816GASS1212OA,
(cut opening for your grille)
88”
8” (203) Stand
Option
Opening for
“G” Panel
14”(356)
Outside Wall
Insulation
Field Supplied
Insulated
Ductwork
Field Supplied Grille with
Insect Screen
Field Supply
Flex Duct Collar
or Fabricate Extension.
Seal to Cabinet and Wall.
G Panel Frame
Seal 4 Sides
Motorized Air Damper Door
Assembled to Frame.
Connect Molex Wire Harness
to Chassis Control Box.
Cut Hole
in Stud
and Seal.
See IOM
with Kit for
Location
and Size.
15' Whip
Drywall
Note 2
Supply Air
Grille Opening
1” Min
5½ Max
62½”
A
Slab
Fig 2D:
H Panel
Drywall Opening
(with frame)
09-12
15-18
24-36
A
17”
20”
24”
B
16”
19”
23”
6”
57½”
B
Slab
Fig 2E:
G Panel
Drywall Opening
(with frame)
2”(51)
2”(51)
Opening 2¼ x
4
¼
(57 x 108)
for A9155801
or similar
horizontal
thermostat turn 2 x
4 box for vertical
thermostat
(Notes 1 and 3)
(1461)
57½”
24
½
”
(622)
24.25”
(616)
(Notes 4 and 5)
One or two layers
of drywall. Set
studs accordingly.
For cabinets with
surface mount
thermostat
For cabinets
with remote
thermostat
Opening 16” x 16”
For Supply Air Grille
A816GASS1616OA,
(cut opening for your grille)
Drywall Openings
for sizes 15-18 and G Panel
on floor
Cabinet
Figure 8
Cabinet
Figure 9
Drywall Openings
for sizes 24-36 and G Panel
With 8” Stand
Notes:
1. All factory-installed whips end with 9 pin molex connector.
2.
Field-supplied 2x4 Box must be a type that the side can be removed so molex can be put inside. Position box
horizontal or vertical for thermostat.
3.
Optional 15, 25, or 35 foot whips (thermostat cable Class 2) available. Whips in BX armor available as special.
4. 1” to 13”(25 to 330) stands available, stands are bulk shipped and must be field installed.
5. When stands or ISO pads are used, make sure riser length and position is calculated correctly. 3” above and
tailpiece always from bottom of cabinet. Stand or ISO pads raises everything up.
6.
For 2” filter, set cabinet 2” (50) minimum from front of drywall.