background image

Adjustments

4-2

750-370

ProFire Q Series Manual

4.2.2 — Gas Adjustments

Low fire combustion analysis typically is 7% to 9% O

and less than .04% CO (400 ppm). A high fire reading typically

is 3% to 4% O

2

 and less than .04% CO.

4.2.3 — Honeywell V48A Gas Valve Adjustment

1.

The bleed valve screw should be open one (1) turn counterclockwise from the fully closed position as a starting 
point.

2.

Adjust the bleed valve in 1/4 turn counterclockwise increments until the V48A gas valve opens at the desired open-

ing speed for a smooth main flame ignition.

3.

The burner should be cycled between adjustments.

4.3 — Electrical Interference Test

Prior to putting the burner into service, conduct the following test to ascertain that main power will not cause the flame

relay to pull in.

Gas Fired Test:

1.

Close the manual gas valves.

2.

Start the burner, the flame relay should not pull in (be energized).

3.

Upon completion of successful test, proceed with startup procedures.

4.

Reconnect the power supply and proceed with startup procedures.

4.4 — Gas System

4.4.1 — Gas Pressure

Gas must be supplied at a pressure high enough to overcome the pressure loss in the burner gas train and furnace

pressure while running at full input. Refer to nameplate inside control panel for gas pressure requirements at train inlet

and manifold. The pressures listed are based on nominal 1000 Btu/cu ft. natural gas at elevations up to 2000 feet above

sea level.

4.4.2 — Gas Flow

The volume of gas is measured in cubic feet as determined by a meter reading. The gas flow rate required depends on

the heating value (Btu/cu ft.). The supplying utility can provide this information as well as pressure correction factors.

To determine the required number of cubic feet per hour of gas, divide burner input (Btu/hr) by the heating value (Btu/
cu ft.).

NOTE: 

The gas train components ship loose, therefore, the bleed valve will need to be installed and adjusted in the field.

NOTE: 

When checking the input rate, Make sure no other equipment is operating on the same meter.

Summary of Contents for profire q

Page 1: ...Manual Part No 750 370 01 2016 ProFire Q Burner Gas Only Installation Operation Maintenance Table Of Contents...

Page 2: ......

Page 3: ...llation Operation and Service Manual Manual Number 750 00370 Release Date January 2016 Information to be filled out by owner Unit Serial Number Date of Installation Distributor Information Name Addres...

Page 4: ...No part of this document may be reproduced stored in a retrieval system or transmitted in any form or by any means without the prior written consent of Industrial Combus tion Cleaver Brooks 351 21st S...

Page 5: ...Canadian Gas Association CGA B149 1 and B149 2 and Canadian Standard Association CSA B140 and B139 for oil burners Installation Codes shall prevail Authorities having jurisdiction should be consulted...

Page 6: ...5 4 1 5 4 0 2 95 4 0 Q6 150 1 500 36 1 2 0 75 1 5 6 2 0 4 0 4 0 Q8 175 1 750 42 3 4 1 0 1 5 6 2 0 4 0 3 45 5 75 Q8 200 2 000 48 3 4 1 0 1 5 6 2 0 4 0 3 80 5 75 Q8 250 2 500 60 3 4 0 75 1 5 10 2 0 4 5...

Page 7: ...11 16 4 3 8 Hinge pivot point in inches Mounting flange to hinge G 22 3 8 25 Hinge swing radius E 17 11 16 20 5 8 Center line to hinge F 4 3 16 3 7 8 Blast tube dimensions in inches Extension L 2 2 Di...

Page 8: ...C 4 11 16 4 3 8 Hinge pivot point in inches Mounting flange to hinge G 22 3 8 25 Hinge swing radius E 17 11 16 20 5 8 Center line to hinge F 4 3 16 3 7 8 Blast tube dimensions in inches Extension L 2...

Page 9: ...894 04111 000 PART DESCRIPTION CONTROL COMPONENTS BURNER SIZE PART NUMBER Display Siemens Full Mod Siemens Q6 Q8 833 05071 000 Cable Display Siemens Full Mod Siemens Q6 Q8 826 00315 000 Controller Si...

Page 10: ...000 Regulator Air Gas 2 Low High Low Pres 918 01319 000 Ball Valves 2 All Low Pressure 941 00128 Regulator Maxitrol 210 1 All High Pressure 817 00617 Valve Gas Diaphragm 1 All High Pressure 940 01103...

Page 11: ...iring Head Assembly w UV Scanner ELECTRODE FLAME ROD SCREW LOCK WASHER BAFFLE WELDMENT STANDOFF LOCK WASHER ORIFICE PLATE SPRING PIN ELECTRODE SPRING PIN NUT LOCK WASHER SCREW UV SCANNER ORIFICE PLATE...

Page 12: ......

Page 13: ...ers 1 2 1 4 Combustion Air Handling System 1 2 1 5 Firing Head 1 3 1 6 Gas System 1 3 1 6 1 Main Gas Train Components 1 4 1 6 2 Pilot Gas Train Components 1 5 1 6 3 Operation 1 5 CHAPTER 2 Installatio...

Page 14: ...l Shutdown 3 4 3 6 Safety Shutdown 3 4 3 7 Startup and Operating 3 5 3 7 1 Gas Burners Bubble Test 3 5 3 7 2 Burners Designed for On Off Operation 3 6 3 7 3 Burners Designed for Low High Low Operation...

Page 15: ...5 Maintenance 5 1 5 1 Overview 5 1 5 2 Control System 5 1 5 2 1 Programming Control 5 2 5 3 Impeller 5 2 5 4 Firing Head Inspection 5 2 5 5 Air Filter Inspection 5 2 5 6 Ignition Electrode Flame Rod 5...

Page 16: ...iv 750 370 ProFire Q Series Manual CHAPTER 6 Troubleshooting 6 1 6 1 Awareness 6 1 6 2 Emergency Shutdown 6 2 6 3 Problem Possible Causes 6 3 STARTUP SERVICE REPORT WARRANTY POLICY...

Page 17: ...manually set firing at any desired rate between minimum and maximum Fully modulated burners include additional safeguards to assure that the burner always returns to the minimum firing position for i...

Page 18: ...tes 90 from low to high position 1 4 Combustion Air Handling System The combustion air handling system consists of two major components Component Details Fusing Control circuit and motor load fusing M...

Page 19: ...ion the fuel metering valve is actuated by the servo The LMV37 regulates the gas flow in proportion to fan speed which is also controlled by the LMV37 For low high low operation the gas flow is contro...

Page 20: ...agm gas valve Main Gas Regulator Regulates gas train pressure to specified pressure required at inlet to the gas train Input is set my the main gas pressure regulator adjustment Main Gas Cocks For man...

Page 21: ...ly modulating burner the butterfly gas valve modulates gas flow to the burner The butterfly valve is positioned by the servo The air is controlled by the LMV37 linkageless system The automatic gas val...

Page 22: ...Introduction 1 6 750 370 ProFire Q Series Manual...

Page 23: ...where the system has a tall chimney The exact height of a chimney requiring draft control is indeterminate but draft regulation is seldom needed for chimneys less than 50 feet high especially with Sco...

Page 24: ...FIGURE 2 1 Combustion Chamber Dimensions Burner Size A in B in C in Combustion Chamber Min Width in Combustion Chamber Min Length in Q6 037 2 6 10 8 20 Q6 055 2 6 10 8 24 Q6 075 2 6 10 10 24 Q6 100 2...

Page 25: ...ed to prevent escape of combustion products into the boiler room The burner mounting flange is designed to provide for a seal The face of the boiler and burner flange must be sealed with a burner flan...

Page 26: ...tion Kit number 880 06384 000 is supplied with the burner and includes the support bracket and hardware A 3 4 NPS pipe must be supplied by others FIGURE 2 3 Support Bracket Installation FIGURE 2 4 Q S...

Page 27: ...ped loose Full modulation gas train components upstream of the butterfly valve are shipped loose These components should be mounted by the installer as close to the burner as practical Normally the co...

Page 28: ...rtain that the operator in charge is properly instructed in the operation and maintenance procedures Before opening the gas shutoff valves read the regulator instructions carefully Open the shutoff va...

Page 29: ...sure required and the pressure setting recorded Item Check Boiler Check the boiler water level Be sure all boiler valves are installed correctly and positioned properly Set the high limit control slig...

Page 30: ...m potentiometers Refer to the Kromschroeder and UGB operation manual for adjustment information See Section 3 7 3 for valve and UGB adjustment For full modulation operation the fan speed and gas setti...

Page 31: ...the flame signal Refer to Flame Safeguard manufacturers instructions for optimal flame signal readings Some flame safeguard amplifier or flame safeguard chassis body has a meter jack for this purpose...

Page 32: ...is ready for startup on the next call for heat 3 5 Manual Shutdown When the burner motor stops close all manual valves 3 6 Safety Shutdown 1 If at any time during the operating cycle a flame failure o...

Page 33: ...rers procedures The unit should be taken out of service if the unit fails any part of the gas valve leak test Any defective part must be replaced prior to putting the equipment back into service 1 Clo...

Page 34: ...3 9 3 7 2 Burners Designed for On Off Operation Adjust main gas regulator and slow opening valve to achieve high fire and smooth ignition 3 7 3 Burners Designed for Low High Low Operation 1 Plumb the...

Page 35: ...te go to parameter 400 3 Use the and buttons to advance until the phase screen is displayed PHXX 4 Turn the burner switch on and burner will advance to phase 36 and purge 5 After purge is complete the...

Page 36: ...modulation rate To exit hold ESC and until the whole display blinks solid indicates auto mode 12 Refer to the Siemens LMV37 manual for a detailed commission sequence After the Siemens LMV37 has been i...

Page 37: ...n the operating cycle always proceeds sequentially through pre purge main flame ignition run and post purge The length of the purge and ignition trial vary according to the type of programmer used Dur...

Page 38: ...med Read and understand starting instructions before attempting to operate the burner Before attempting to start the burner the following checks must be made An ultraviolet flame sensor electrical spa...

Page 39: ...djustment on Gas Efficient combustion cannot be properly judged by flame appearance although it may help in making preliminary settings The proper settings of air fuel ratios must be determined by flu...

Page 40: ...ccessful test proceed with startup procedures 4 Reconnect the power supply and proceed with startup procedures 4 4 Gas System 4 4 1 Gas Pressure Gas must be supplied at a pressure high enough to overc...

Page 41: ...after tripping To reset allow gas pressure to rise and press the manual reset button 4 4 6 High Gas Pressure Switch Turn the adjusting screw until the indicator moves to a pressure setting slightly ab...

Page 42: ...4 5 Parallel Positioning Adjustment For parallel positioning systems refer to the control manufacturer s documentation and to the accompanying wiring diagram for information on adjusting the system I...

Page 43: ...beyond regular inspection Examine electrical connections Keep the controls clean Remove any dust from the interior of the control Covers should be left on controls at all times Keep the control cabine...

Page 44: ...uld verify safety shutdown with a safety lock out upon failure to ignite the pilot or the main flame and upon loss of flame Each of these conditions should be checked on a scheduled basis The safety c...

Page 45: ...y is supported by a socket in the diffuser and gas inlet tube No adjustment is required except proper positioning of the electrode wire 5 7 Flame Scanner The scanner must be clean Even a small amount...

Page 46: ...ose wiring connections If there is proper voltage at the valve coil and the valve still fails to open replace the coil Refer to manufacturer s bulletin for correct procedure in coil replacement Should...

Page 47: ...ator Refer to instructions Air Filter Operator Refer to instructions WEEKLY Firing Rate Control Operator Verify factory settings Igniter Operator Make visual inspection Check flame signal strength Mai...

Page 48: ...Maintenance 5 6 750 370 ProFire Q Series Manual...

Page 49: ...condition Refer to the control bulletin for specifics and suggested remedies Familiarity with the programmer and other controls in the system may be obtained by studying the contents of this manual Kn...

Page 50: ...l shut off valves on the fuel supply line The unit can also be shut down with the main electrical power disconnect Inspect the burner carefully and troubleshoot before re starting the unit Follow inst...

Page 51: ...ock circuit not completed a Fuel valve auxiliary switch not closed No Ignition 1 Lack of spark a Electrode grounded or porcelain cracked b Improper electrode setting c Loose terminal on ignition cable...

Page 52: ...or open circuit in running interlock circuit d The flame failure light is energized by ignition failure main flame failure inadequate flame signal or open control in the running interlock circuit 7 Im...

Page 53: ...PPM Flame Failure Smoke Bacharach N A N A N A Combustion Air Switch Combustion Eff High Purge Switch Stack Draft W C Low Fire Interlock Furnace Pressure W C Oil Pressure Switch N A N A Blast Tube Pre...

Page 54: ...750 370 ProFire Q Series Manual...

Page 55: ...ent Warranty Adjustment Buyer must make claim of any breach of any warranty by written notice to the Company s home office within thirty 30 days of the discovery of any defect The Company agrees at it...

Page 56: ...any s liability for breach of implied if any and express warranties representations instructions or defects from any cause in connection with the sale or use of the equipment THE COMPANY SHALL NOT BE...

Page 57: ......

Page 58: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...

Reviews: