750-370
ProFire Q Series Manual
2-3
Installation
FIGURE 2-2.
Burner Model/Boiler HP
2.5 — Installation
Allow enough clearance at the bottom of the burner to allow the proper air supply. Many boilers, including some Scotch
Marine types, do not have sufficiently rigid front plates and require additional support under the burner base. Boilers
operating with the combustion pressure above atmospheric pressure must be sealed to prevent escape of combustion
products into the boiler room. The burner mounting flange is designed to provide for a seal. The face of the boiler and
burner flange must be sealed with a burner flange gasket (ensure burner flange gasket is installed properly). Make sure
the dry oven and burner blast tube are concentric. For maximum safety, it is recommended that boilers not operating
under pressure should also be sealed.
Burner Model
Boiler HP
A (in.)
B (in.)
Q6-037
9
8
20
Q6-055
13
8
24
Q6-075
18
10
24
Q6-100
25
12
24
Q6-130
30
12
36
Q6-150
36
14
36
Q8-175
42
14
48
Q8-200
50
16
48
Q8-250
60
16
48
B
A
750-00512-000
Summary of Contents for profire q
Page 2: ......
Page 12: ......
Page 22: ...Introduction 1 6 750 370 ProFire Q Series Manual...
Page 48: ...Maintenance 5 6 750 370 ProFire Q Series Manual...
Page 54: ...750 370 ProFire Q Series Manual...
Page 57: ......
Page 58: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...