Operation
3-4
750-370
ProFire Q Series Manual
Refer to the manufacturer’s literature on programming controls and burner wiring diagrams for detailed information.
1.
Begin starting sequence, with burner switch off, and with all manual valves closed. Switch main power on.
2.
Open the main manual gas shutoff valve.
3.
Manually reset the high and low gas pressure switches.
4.
When the burner motor starts, partially open the leak test gas valve.
5.
When the main fuel lamp lights indicating ignition flame proven, slowly open the leak test valve downstream of the
main gas valve(s).
Refer to the manufacturer’s literature on primary control sequence of operations.
3.4 — Automatic Shutdown
Limit or operating controls open:
1.
Fuel valves close. Main fuel lamp goes off. Flame safeguard timer starts.
2.
Flame safeguard timer and burner motor stop. Burner is ready for startup on the next call for heat.
3.5 — Manual Shutdown
When the burner motor stops, close all manual valves.
3.6 — Safety Shutdown
1.
If at any time during the operating cycle a flame failure occurs, the burner shuts down as in “Automatic Shutdown”,
with an additional post-purge, and the flame failure lamp is energized.
Read the Flame Safeguard manual and fully understand its contents before attempting to operate this equipment. If the
manual is not read and understood, serious personal injury or death may result.
Should a starting failure occur for any reason, combustible fumes may fill the combustion chamber. Never attempt to re-
light the burner under these conditions. The combustion chamber must first be purged before re-lighting.
Keep fingers away from the combustion air intake below the damper. The damper is actuated with sufficient force to cause
severe injury. Always make high and intermediate rate adjustments when the burner has reached low fire position. Do not
disturb the low fire setting.
!
Warning
!
Warning
!
Warning
Summary of Contents for profire q
Page 2: ......
Page 12: ......
Page 22: ...Introduction 1 6 750 370 ProFire Q Series Manual...
Page 48: ...Maintenance 5 6 750 370 ProFire Q Series Manual...
Page 54: ...750 370 ProFire Q Series Manual...
Page 57: ......
Page 58: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...