Maintenance
5-2
750-370
ProFire Q Series Manual
5.2.1 — Programming Control
This control requires no adjustment, nor should any attempt be made to alter contact settings or timing logic. Those
programmers with contacts may require occasional cleaning. If so, follow instructions given in the manufacturer's
bulletin. Never use abrasive materials. The manufacturer's bulletin also contains troubleshooting information. The
flame detector lens should be cleaned as often as conditions demand. A periodic safety check procedure should be
established to test the complete safeguard system. Tests should verify safety shutdown with a safety lock out upon
failure to ignite the pilot or the main flame, and upon loss of flame. Each of these conditions should be checked on a
scheduled basis. The safety check procedures are contained in the manufacturer's bulletin.
5.3 — Impeller
The blower uses a backward curved impeller and a die cast aluminium housing. The blower requires no adjustment.
5.4 — Firing Head Inspection
Release the side cover and pull the firing head out of the burner housing. Inspect the flame scanner lens to be sure it is
clean. Inspect the lead wire to the ignition electrode. It must be firmly attached and the insulation should be clean and
free of cracks.
5.5 — Air Filter Inspection
The air filter if provided needs to be inspected daily and replaced on an as needed basis.
Summary of Contents for profire q
Page 2: ......
Page 12: ......
Page 22: ...Introduction 1 6 750 370 ProFire Q Series Manual...
Page 48: ...Maintenance 5 6 750 370 ProFire Q Series Manual...
Page 54: ...750 370 ProFire Q Series Manual...
Page 57: ......
Page 58: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...