Standard Q Series Specifications
Burner
Model
Gas
Input
MBtu/hr
BHP
@80%
Eff.
Blower
Motor
HP
Furnace
Pressure
(“w.c.”)
Gas
Train
Size
(in.)
Min. Gas
Pressure
Required
(“w.c)
Low
Pressure
Gas Train
Pipe Size
(in.)
Low Gas
Pressure
Inlet
(“w.c.)
Air Inlet
Orifice
Size (in.)
Fresh
Air Inlet
Size
(in.)
Q6-037
375
9
1/2
1.0
1.5
4
1.5
4.0
1.25
4.0
Q6-055
550
13
1/2
1.0
1.5
4
1.5
4.0
1.50
4.0
Q6-075
750
18
1/2
1.0
1.5
4
1.5
4.0
1.80
4.0
Q6-100
1,000
24
1/2
1.0
1.5
4
1.5
4.0
2.25
4.0
Q6-130
1,250
30
1/2
1.0
1.5
4
1.5
4.0
2.95
4.0
Q6-150
1,500
36
1/2
0.75
1.5
6
2.0
4.0
-
4.0
Q8-175
1,750
42
3/4
1.0
1.5
6
2.0
4.0
3.45
5.75
Q8-200
2,000
48
3/4
1.0
1.5
6
2.0
4.0
3.80
5.75
Q8-250
2,500
60
3/4
0.75
1.5
10
2.0
4.5
-
5.75
NOTES:
1.
Gas input based on natural gas at 1,000 Btu/cu. ft. and 0.60 gravity.
2.
For total pressure at manifold, add furnace pressure.
3.
Boiler overall efficiency of 80% estimated.
4.
Blower wheel and motor HP is based on altitude up to 2,000 ft. above sea level. For higher altitude or 50 Hz.
applications, consult factory.
5.
Firing at higher furnace pressures de-rates the burner by approximately 5% per 1/2” of additional pressure.
Consult factory.s
6.
Blower Motor Voltage/ Ph. 60 Hz: 115/1
Summary of Contents for profire q
Page 2: ......
Page 12: ......
Page 22: ...Introduction 1 6 750 370 ProFire Q Series Manual...
Page 48: ...Maintenance 5 6 750 370 ProFire Q Series Manual...
Page 54: ...750 370 ProFire Q Series Manual...
Page 57: ......
Page 58: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...