background image

        Maintenance

 (continued)

 

18 

Step 10: 

With contact brush attached, remove the brush adapter nut from the high voltage end cap. 

Step 11: 

Inspect  the  dielectric,  end  caps  and  cathode  for  breakage,  corrosion  or  debris.  Clean  and/or  replace  parts  as 
necessary.  If  cleaning  and/or  parts  replacement  is  not  required,  re-assemble  the  reaction  chamber  per  the 
instructions below. 

Assembly and Re-installation

 

Step 1: 

Make sure the glass dielectric is clean (free of dust, dirt, grease, oils, etc.). 

Step 2: 

Prepare the end caps for re-assembly by replacing the O-rings. Thread the hex brush adapter nut, with contact 
brush attached, onto the end of the high voltage end cap (cap with the white power lead attached) center screw.  

Step 3: 

Using a gentle twisting motion, press the 

non

-high voltage end cap onto the heat sink/cathode assembly until

 

flush with the heat sink cooling fins. 

Note:  See Figure 8-3 for correct orientation of end cap.

 

Step 4: 

Slide the four end cap retaining screws through the holes in the non-high voltage end cap, aligning them with 
the heat sink screw bosses. Thread screws into screw bosses until heads are snug against the end cap. 

Step 5: 

Roll the high voltage anode (foil-like material) lengthwise, preserving the 

longer

 dimension. Insert the rolled

 

anode into the dielectric. Center the anode in the dielectric (approximately 1/2” from either end of the glass), 
making sure it is rolled squarely. 

Step 6: 

Slide  the  dielectric  into  the  heat  sink/cathode  assembly.  Seat  the  dielectric  into  the  O-rings  of  the  non-high 
voltage end cap by applying pressure with a gentle twisting motion. (There must not be any dirt, debris, oils or 
fingerprints on the dielectric upon re-installation). 

Step 7: 

Slowly

  insert  the  high  voltage  end  cap  assembly  into  the  dielectric. 

Note:  Do  not  bend  center  wire  of  the 

brush during this procedure.

  It is normal for the 

bristles

 to bend. Using a gentle twisting motion, press the 

high voltage end cap onto the heat sink/cathode assembly until flush with the heat sink cooling fins.

 

Step 8: 

Slide the four end cap retaining screws through the holes in the end cap, aligning them with the heat sink screw 
bosses. Thread screws into screw bosses until heads are snug against the end cap. 

Step 9

:

 

Re-install  complete  reaction  chamber  assembly  into  the  ozone  generator  by  following  the  “Removal  and 
Disassembly” instructions in reverse order, from Step 6 to Step 2.  Follow steps outlined in Chapter 7, “Start-
Up and Calibration,” to re-start the ozone system. 

 

2” Pressurized Reaction Chamber - Exploded View 

Figure 8-3 
 

 

 

   

 

 

 

 

 

 

 

 

 

 

 
 

Ozone Outlet 

Fitting 

Bottom End Cap 

Glass Dielectric 

High Voltage Anode 

Stainless Steel Clamp 

Contact Brush 

Brush Adapter Nut 

High Voltage End Cap 

End Cap Retaining 

Screw and Washer 

Oxygen Inlet Fitting 

Viton Washer 

 

 

 

 

 

 

 

 

 

Stainless Steel 

Washer 

High Voltage 
Lead 

Heat Sink and Cathode 

Summary of Contents for CD1500P

Page 1: ...s a component only Tested and certified by WQA to NSF ANSI 50 as a component only ClearWater Tech LLC Integrated Ozone Systems 850 E Capitolio Way San Luis Obispo Ca 93401 805 549 9724 Fax 805 549 030...

Page 2: ...o achieve the ozone output and longevity of the ozone generator A pounds per square inch PSI regulator must be installed when using plant air feed gas This regulator must be set to a maximum of 10 PSI...

Page 3: ...m of extremely tiny bubbles These bubbles must be as small as possible in order to increase the ratio of bubble surface area to the amount of ozone entering the water Depending on the application and...

Page 4: ...s detectable at very low concentrations 0 02 ppm which is far below OSHA s maximum permissible exposure level of 0 1 ppm HIGH VOLTAGE WARNING CLEARWATER TECH OZONE GENERATORS OPERATE AT HIGH VOLTAGE D...

Page 5: ...ipment 7 The electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422 20 of the National Electrica...

Page 6: ...justment chemical injection point must be located downstream of the residual sanitizer injection point if so equipped In a Full Flow plumbing configuration see Figure 4 2 without recirculation locate...

Page 7: ...ical print or as dictated by equipment layout and serviceability considerations Do not secure booster pump and contact vessel to housekeeping pads at this point Dry fit plumbing as appropriate to insu...

Page 8: ...he two holes for mounting the L bracket to the wall The bracket should be located so that the 6 clamp assembly will be approximately 12 from the top of the contact column Drill a 1 2 hole at each of t...

Page 9: ...Base Flange Gasket Base Flange Nuts Washers 8ea Contact Column Exploded View Figure 4 4 Contact Column Installation Diagram Figure 4 3 6 Clamp Assembly Bolts nuts with bolt Nut washers 2ea Unistrut cu...

Page 10: ...AWG wire located at the bottom panel of the ozone generator see Appendix Section A can be interfaced to any control device i e pressure switch vacuum switch flow switch float switch ORP controller PPM...

Page 11: ...Preparation System Power 120VAC systems only plug the power cord into main power 240VAC systems only the power cord must be hard wired to the main power source Black L1 White L2 N and Green Ground No...

Page 12: ...y Step 3 Mount indicator cartridge on a suitable flat surface using the Clic mounting clamps provided Notes The indicator cartridge must be mounted vertically The indicator cartridge does not have a d...

Page 13: ...vertical position and the drain holes are below the level of the ozone generators ozone outlet fitting One clamp should be located so it fits around the Riser Tube Elbow and the other so it fits aroun...

Page 14: ...the injector manifold until the needle moves into the green zone If the needle is in the red zone on the vacuum in Hg side of the gauge gradually open the ball valve on the injector manifold until the...

Page 15: ...e it will open causing a loss of vacuum A loss of vacuum means ozone cannot flow from the vacuum break which in turn can cause an ozone leak Note If the vacuum break must be refilled with water discon...

Page 16: ...ary by following the steps outlined in the Start Up Calibration section Ozone Generator Indicator Lights Check the Main Power indicator light at the bottom of the ozone generator and Ozone LED s at th...

Page 17: ...one output LED will illuminate when ozone drive is being generated The LED will also pulse as the output increases or decreases with either the Manual Ozone Output Control located on the bottom of the...

Page 18: ...and or operating conditions in the equipment area will dictate the required frequency of this procedure Ozone Generators Cooling Fan Filters Clean or replace the cooling fan filter elements as requir...

Page 19: ...ielectric approximately 1 2 from either end of the glass making sure it is rolled squarely Step 6 Slide the dielectric into the heat sink cathode assembly Seat the dielectric into the O rings of the n...

Page 20: ...normal for some water to be flowing from the injector during this procedure Contact Vessel Cleaning Contact Column only Inspect the diffuser slots at the top of the contact column riser tube If they...

Page 21: ...place compressor or pink or white ATF module as required Replace indicating desiccant Unit is making excessive noise Unit not properly secured to floor Place unit on a flat level surface Shipping dama...

Page 22: ...ing Fault LED The Ozone Output LED s The remote 4 20mA control signal is not Check for loose wires or connections not responding to the remote sensed by the 4 20mA control board 4 20mA control signal...

Page 23: ...libration Debris on seat of vacuum break flapper valve Clean seat of flapper See Maintenance Procedures Annual Low vacuum Hydraulics Pneumatics out of adjustment See Start Up Calibration Steps 1 4 Def...

Page 24: ...ns Shown ClearWater Tech OXS90 Air Prep System with Cover Shown ClearWater Tech OXS90 Air Prep System with out Cover AIR PREP SYSTEM SPECIFICATIONS OXYGEN OUTPUT SCFH OXS90 Workhorse 12c 15 5 h x 17 w...

Page 25: ...Drive Board and Drive Transformer under board Reaction Chamber Power Supply Inline Particulate Filter 4 20mA Control Board Pressure Switch Cover Safety Switch External Loop Remote 4 20mA Control Lead...

Page 26: ...rs Drive Board and Drive Transformer XFMR under boards Inline Particulate Filter Power Supply Pressure Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Air Pre...

Page 27: ...00P RCC10 Dielectric Anode 2 RCC71 Non High Voltage End Cap Contact Dealer High Voltage End Cap Contact Dealer O ring Set ORS40 Drive Module Complete CD2000P DRM60 Drive Module Transformer HVT275 Driv...

Page 28: ...1 Filter Inline particulate filter FUS20 2 Fuse Bussmann MDL 5 5 amp 250VAC Slow Blow Main Power ORG110 4 O ring 2 CD reaction chamber pressurized end cap large ORG120 4 O ring 2 CD reaction chamber p...

Page 29: ...try Module With Fuses High Voltage Transformer Drive Board Remote 4 20mA Ozone Output Control Orange Purple Manual Ozone Output Control Fan Power Supply Cover Safety Switch Power Supply 4 20mA Control...

Page 30: ...afety Switch Power Supply Power Supply Fan Fan 24VDC 24VDC 24VDC 24VDC Manual Ozone Output Control Remote 4 20mA Ozone Output Control Orange Purple External Loop 4 20mA Control Board Variable Output S...

Page 31: ...30 Drive Module Input Voltages Shown Dual HO Drive Module APPENDIX Section E...

Page 32: ...nced with the product and or part must be clearly described The RGA number must appear prominently on the exterior of the shipped box es The product and or part must be packaged either in its original...

Reviews: