background image

 

   

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION PROCEDURES – 

Plumbing

              

       CHAPTER 4

 

 

 

The ozone system should be plumbed using either a sidestream or full flow configuration.  The 
sidestream  loop  method  takes 

a  portion

  of  the  water  from  the  main  flow  (see  Figure  4-1)  and 

diverts it into a sidestream 

downstream

 of the filter (if so equipped). Ozone is introduced into the 

sidestream water and is allowed contact time with the water before it is returned to the main flow 
at a point downstream of all other  equipment (heaters, solar panels, etc., if so equipped) in the 
circulation system.  A booster pump is usually  employed to compensate for the flow  restriction 
caused  by  the  sidestream  loop  and  the injector  manifold.  If  a  halogen-type  residual  sanitizer  is 

utilized, its injection point should be as far downstream as possible from the point at which the sidestream water returns to 
the  main  flow.  In  a  full  flow  configuration,  the  same  system  components  are  usually  involved  and  appear  in  the  same 
order with respect to the direction of flow. However, 

all

 the water in the main flow is allowed contact time with the ozone 

(see Figure 4-2). A booster pump may be necessary to maintain proper flow requirements. If employed, the booster pump 
is located 

upstream

 of the point at which the ozone injector manifold is installed.

 

NOTES: 

•  Adequate  use  of  unions  and  isolation  valves  is 

strongly  recommended  to  facilitate  maintenance 
and repairs. 

 

•  Use Schedule 80 PVC for all plumbing connections 

wherever  possible.    Plumbing  size  requirements 
are  dictated  by  the  water  flow  characteristics  of 
the system. 

 

•  Make  sure  to  use  proper  plumbing  practices  and 

secure  all  plumbing  and  system  equipment 
according to local codes. 

 

 

 

• Ozone is a powerful oxidizer and  will degrade certain 

materials.  Use  ozone-compatible  plumbing  materials 
for  section(s)  of  the  system  that  will  come  in  contact 
with ozone dissolved in water. The following is a list of 
materials that are compatible with ozone: 

• PVC 

 

• Stainless Steel (300 series) 

• CPVC 

 

• Viton 

• Kynar 

 

• EPDM 

• Teflon 

 

• Concrete 

 

•  Depending  on  the  application,  other  components  (psi 

gauge,  flow  meter,  etc.)  may  be  installed  to  assist  in 
monitoring system parameters.

Step 1:

 Arrange the ozone system equipment (booster pump, injector and contact vessel) according to mechanical print 

or as dictated by equipment layout and serviceability considerations. Do not secure booster pump and contact 
vessel  to  housekeeping  pads  at  this  point.  Dry  fit  plumbing  as  appropriate  to  insure  proper  fit  and  location 
before making permanent connections. 

Step 2:

  Install  a  tee  or  plumbing  saddle  into  the  main  water  line  after  the  filter  (if  so  equipped)  and  before  the  flow 

diversion  mechanism.  The  purpose  of  the  mechanism  is  to  restrict  water  flow  so  water  is  diverted  into  the 
sidestream  (see  Figure  4-1).  If  such  a  mechanism  is  not  present  in  the  system  (such  as  a  heater  bypass  valve, 
etc.), it will require installation of a valve (butterfly, gate or ball) or a flow controller. 

Step 3:

 

Plumb a line from the tee or plumbing saddle to the booster pump.  For serviceability of the equipment in the 
sidestream loop, be sure to install an isolation valve between the tee or saddle and the booster pump. 

Step 4:

 Plumb from the booster pump to the injector manifold. Make sure to note the correct direction of flow, indicated 

by a blue arrow on the inlet side of the manifold body. The check valve assembly is strapped to the manifold 
using wire ties. Remove the assembly; using Teflon® tape, install it onto the top opening of the injector.

 

Step 5:

 

Plumb from the injector manifold to the inlet side of the contact vessel. To reduce possible backpressure to the 

injector, minimize the number of elbows between the injector manifold and contact vessel. The contact vessel is 
a specified size, determined by water flow requirements. ClearWater Tech contact columns and the 30, 40, 80, 
and 120-gallon contact tanks have inlet 

and

 outlet fittings on the bottom of the vessel and are designated with 

arrows showing the direction of flow

. Note: The inlet and outlet arrows on the contact tanks are under the 

base  of  the  tank.

  The  inlet  on  the  264,  463  and  850-gallon  tanks  is  located  at  the  top  with  the  outlet  at  the 

bottom. 

Step 6:

 Using a tee or plumbing saddle, plumb from the outlet of the contact vessel back into the main water line. For 

serviceability of the equipment in the side stream loop, be sure to install an isolation valve between the outlet 
fitting on the contact vessel and before returning to the main water line. 

Step 7: 

Secure  the  booster  pump  and  contact  vessel  to  solid  mounting  surfaces  using  appropriate  hardware  and 
according  to  local  codes.  If  installing  a  ClearWater  Tech  contact  column,  use  a  ClearWater  Tech  contact 

Summary of Contents for CD1500P

Page 1: ...s a component only Tested and certified by WQA to NSF ANSI 50 as a component only ClearWater Tech LLC Integrated Ozone Systems 850 E Capitolio Way San Luis Obispo Ca 93401 805 549 9724 Fax 805 549 030...

Page 2: ...o achieve the ozone output and longevity of the ozone generator A pounds per square inch PSI regulator must be installed when using plant air feed gas This regulator must be set to a maximum of 10 PSI...

Page 3: ...m of extremely tiny bubbles These bubbles must be as small as possible in order to increase the ratio of bubble surface area to the amount of ozone entering the water Depending on the application and...

Page 4: ...s detectable at very low concentrations 0 02 ppm which is far below OSHA s maximum permissible exposure level of 0 1 ppm HIGH VOLTAGE WARNING CLEARWATER TECH OZONE GENERATORS OPERATE AT HIGH VOLTAGE D...

Page 5: ...ipment 7 The electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422 20 of the National Electrica...

Page 6: ...justment chemical injection point must be located downstream of the residual sanitizer injection point if so equipped In a Full Flow plumbing configuration see Figure 4 2 without recirculation locate...

Page 7: ...ical print or as dictated by equipment layout and serviceability considerations Do not secure booster pump and contact vessel to housekeeping pads at this point Dry fit plumbing as appropriate to insu...

Page 8: ...he two holes for mounting the L bracket to the wall The bracket should be located so that the 6 clamp assembly will be approximately 12 from the top of the contact column Drill a 1 2 hole at each of t...

Page 9: ...Base Flange Gasket Base Flange Nuts Washers 8ea Contact Column Exploded View Figure 4 4 Contact Column Installation Diagram Figure 4 3 6 Clamp Assembly Bolts nuts with bolt Nut washers 2ea Unistrut cu...

Page 10: ...AWG wire located at the bottom panel of the ozone generator see Appendix Section A can be interfaced to any control device i e pressure switch vacuum switch flow switch float switch ORP controller PPM...

Page 11: ...Preparation System Power 120VAC systems only plug the power cord into main power 240VAC systems only the power cord must be hard wired to the main power source Black L1 White L2 N and Green Ground No...

Page 12: ...y Step 3 Mount indicator cartridge on a suitable flat surface using the Clic mounting clamps provided Notes The indicator cartridge must be mounted vertically The indicator cartridge does not have a d...

Page 13: ...vertical position and the drain holes are below the level of the ozone generators ozone outlet fitting One clamp should be located so it fits around the Riser Tube Elbow and the other so it fits aroun...

Page 14: ...the injector manifold until the needle moves into the green zone If the needle is in the red zone on the vacuum in Hg side of the gauge gradually open the ball valve on the injector manifold until the...

Page 15: ...e it will open causing a loss of vacuum A loss of vacuum means ozone cannot flow from the vacuum break which in turn can cause an ozone leak Note If the vacuum break must be refilled with water discon...

Page 16: ...ary by following the steps outlined in the Start Up Calibration section Ozone Generator Indicator Lights Check the Main Power indicator light at the bottom of the ozone generator and Ozone LED s at th...

Page 17: ...one output LED will illuminate when ozone drive is being generated The LED will also pulse as the output increases or decreases with either the Manual Ozone Output Control located on the bottom of the...

Page 18: ...and or operating conditions in the equipment area will dictate the required frequency of this procedure Ozone Generators Cooling Fan Filters Clean or replace the cooling fan filter elements as requir...

Page 19: ...ielectric approximately 1 2 from either end of the glass making sure it is rolled squarely Step 6 Slide the dielectric into the heat sink cathode assembly Seat the dielectric into the O rings of the n...

Page 20: ...normal for some water to be flowing from the injector during this procedure Contact Vessel Cleaning Contact Column only Inspect the diffuser slots at the top of the contact column riser tube If they...

Page 21: ...place compressor or pink or white ATF module as required Replace indicating desiccant Unit is making excessive noise Unit not properly secured to floor Place unit on a flat level surface Shipping dama...

Page 22: ...ing Fault LED The Ozone Output LED s The remote 4 20mA control signal is not Check for loose wires or connections not responding to the remote sensed by the 4 20mA control board 4 20mA control signal...

Page 23: ...libration Debris on seat of vacuum break flapper valve Clean seat of flapper See Maintenance Procedures Annual Low vacuum Hydraulics Pneumatics out of adjustment See Start Up Calibration Steps 1 4 Def...

Page 24: ...ns Shown ClearWater Tech OXS90 Air Prep System with Cover Shown ClearWater Tech OXS90 Air Prep System with out Cover AIR PREP SYSTEM SPECIFICATIONS OXYGEN OUTPUT SCFH OXS90 Workhorse 12c 15 5 h x 17 w...

Page 25: ...Drive Board and Drive Transformer under board Reaction Chamber Power Supply Inline Particulate Filter 4 20mA Control Board Pressure Switch Cover Safety Switch External Loop Remote 4 20mA Control Lead...

Page 26: ...rs Drive Board and Drive Transformer XFMR under boards Inline Particulate Filter Power Supply Pressure Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Air Pre...

Page 27: ...00P RCC10 Dielectric Anode 2 RCC71 Non High Voltage End Cap Contact Dealer High Voltage End Cap Contact Dealer O ring Set ORS40 Drive Module Complete CD2000P DRM60 Drive Module Transformer HVT275 Driv...

Page 28: ...1 Filter Inline particulate filter FUS20 2 Fuse Bussmann MDL 5 5 amp 250VAC Slow Blow Main Power ORG110 4 O ring 2 CD reaction chamber pressurized end cap large ORG120 4 O ring 2 CD reaction chamber p...

Page 29: ...try Module With Fuses High Voltage Transformer Drive Board Remote 4 20mA Ozone Output Control Orange Purple Manual Ozone Output Control Fan Power Supply Cover Safety Switch Power Supply 4 20mA Control...

Page 30: ...afety Switch Power Supply Power Supply Fan Fan 24VDC 24VDC 24VDC 24VDC Manual Ozone Output Control Remote 4 20mA Ozone Output Control Orange Purple External Loop 4 20mA Control Board Variable Output S...

Page 31: ...30 Drive Module Input Voltages Shown Dual HO Drive Module APPENDIX Section E...

Page 32: ...nced with the product and or part must be clearly described The RGA number must appear prominently on the exterior of the shipped box es The product and or part must be packaged either in its original...

Reviews: