CleanWater Tech CD1500P Installation & Operation Manual Download Page 14

 

13 

 

START-UP & CALIBRATION                                     

CHAPTER 7 

 
The  previous  sections  of  this  manual  have  involved  comparatively  static  procedures  –  making 
electrical and pneumatic  connections, fitting pipe, etc. This section involves the dynamic process of 
starting  up  and  balancing  the  components  of  the  ozone  system,  including  initiating  water  flow, 
making air and water flow adjustments, etc. 
 
Maximum performance and reliability is achieved when the prescribed air flow is maintained at the ozone generator while 
the system is operating under pressure. Air from the air preparation system is flowing 

through

 the ozone generator under 

pressure, and 

from

 the ozone generator under a slight vacuum (created by the ozone injector manifold).  The change from 

pressure to vacuum occurs after the stainless steel ozone outlet needle valve on the ozone generator.  
 

Air Preparation System, Ozone Generator & Ozone Injector 

Warning: 

Disconnect the External Loop dry contact from the ozone generator while performing all start-up 

procedures.

  

Failure to do so may result in ozone escaping to atmosphere. 

Step 1: 

Make  sure  all  isolation  valves  in  the  ozone  water  system  are  open  (Figures  4-1  or  4-2  show  recommended 
isolation valve locations). 

Step 2: 

Start-up hydraulics.  Allow the  water system to reach hydraulic equilibrium (contact vessel full, off-gas vent 
operating, etc.) and observe  for plumbing leaks. 

Note: Water flow 

must

 be  established through  the  main 

water pump and the ozone system booster pump (if so equipped). 

 

Step 3: 

Close the ball valve on the injector manifold about half way.

 

Step 4:

 

Using  your  thumb,  check  for  the  presence  of  vacuum  (suction)  at  the 
ozone  injection  manifold  check  valve  assembly  or  use  a  ClearWater 
Tech vacuum test assembly to check vacuum  at the injector port. If no 
suction  is  present,  continue  to  close  the  ball  valve  on  the  injector 
manifold  until  vacuum  is  detected.  If  using  the  vacuum  test  assembly, 
check the VAC/PSI gauge for vacuum.  If the needle is in the red zone 
on the pressure (PSI) side of the gauge, gradually close the ball valve on 
the injector manifold until the needle moves into the green zone.  If the 
needle  is  in  the  red  zone  on  the  vacuum  (in.Hg)  side  of  the  gauge, 
gradually  open  the  ball  valve  on  the  injector  manifold  until  the  needle 
moves into the green zone. While vacuum is in the green zone you must 
be able to achieve proper  SCFH  (Standard  Cubic Feet per  Hour) of air flow  (see the  “Pneumatic  Operating 
Parameters” chart for venturi SCFH required, Figure 7-1). 

Step 5:

  

Make sure electrical power is on to all ozone system electrical components. The main power switch of the air 
preparation  system  must  be  in  the  “ON”  position  (if  so  equipped)  (see  Figure  6-2).    The  air  preparation 
system  must  be  set  to  “atmospheric  pressure”  prior  to  full  start  up  of  the  system.    Disconnect  the  oxygen 
delivery line from each oxygen concentrator (if delivery has already been attached). 

Note: This should have 

been completed in Step 5 of “Installation Procedures - Electrical.”

 

Step 1:

  

Check to make sure the compressor of the air preparation system is operating.

Step 2: 

 

Using the air flow gauge adjustment valve on the air preparation system (see Figure 6-2), adjust the 

air flow  according to the “Air prep system air flow” specifications outlined in Figure 7-1. 

Note: When the 

system  is  under  normal  operation,  the  air  flow  will  drop  from  the  initial  setting  due  to  the  air 
preparation  system  being  under  back  pressure.

 

DO 

NOT

  READJUST  THE  AIR  FLOW  GAUGE 

ADJUSTMENT VALVE. 

Step 6: 

Connect the Teflon

 ozone delivery line from the vacuum break to the ozone inlet fitting located at the ozone 

injection manifold check valve assembly. 

 

Step 7:  

Using the stainless steel ozone outlet needle valve located at the bottom the ozone generator (see Appendix,  
Section  A),  adjust  the  backpressure  of  the  ozone  reaction  chambers  to  10  PSI.  Check  the  PSI  gauge  on  the 
front panel of the ozone generator, which measures this backpressure. If there is insufficient backpressure the 
needle  valve  may  be  closed  slightly;  similarly,  if  there  is  too  much  backpressure  the  valve  may  be  opened 
slightly

.    Note:  The  lock  nut  on  the  needle  valve  must  be  loosened  prior  to  adjustment  and  tightened 

after adjustment.

 Due to the pressure switch installed, the PSI gauge must achieve 9 PSI before ozone will 

begin production. 

 

Summary of Contents for CD1500P

Page 1: ...s a component only Tested and certified by WQA to NSF ANSI 50 as a component only ClearWater Tech LLC Integrated Ozone Systems 850 E Capitolio Way San Luis Obispo Ca 93401 805 549 9724 Fax 805 549 030...

Page 2: ...o achieve the ozone output and longevity of the ozone generator A pounds per square inch PSI regulator must be installed when using plant air feed gas This regulator must be set to a maximum of 10 PSI...

Page 3: ...m of extremely tiny bubbles These bubbles must be as small as possible in order to increase the ratio of bubble surface area to the amount of ozone entering the water Depending on the application and...

Page 4: ...s detectable at very low concentrations 0 02 ppm which is far below OSHA s maximum permissible exposure level of 0 1 ppm HIGH VOLTAGE WARNING CLEARWATER TECH OZONE GENERATORS OPERATE AT HIGH VOLTAGE D...

Page 5: ...ipment 7 The electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422 20 of the National Electrica...

Page 6: ...justment chemical injection point must be located downstream of the residual sanitizer injection point if so equipped In a Full Flow plumbing configuration see Figure 4 2 without recirculation locate...

Page 7: ...ical print or as dictated by equipment layout and serviceability considerations Do not secure booster pump and contact vessel to housekeeping pads at this point Dry fit plumbing as appropriate to insu...

Page 8: ...he two holes for mounting the L bracket to the wall The bracket should be located so that the 6 clamp assembly will be approximately 12 from the top of the contact column Drill a 1 2 hole at each of t...

Page 9: ...Base Flange Gasket Base Flange Nuts Washers 8ea Contact Column Exploded View Figure 4 4 Contact Column Installation Diagram Figure 4 3 6 Clamp Assembly Bolts nuts with bolt Nut washers 2ea Unistrut cu...

Page 10: ...AWG wire located at the bottom panel of the ozone generator see Appendix Section A can be interfaced to any control device i e pressure switch vacuum switch flow switch float switch ORP controller PPM...

Page 11: ...Preparation System Power 120VAC systems only plug the power cord into main power 240VAC systems only the power cord must be hard wired to the main power source Black L1 White L2 N and Green Ground No...

Page 12: ...y Step 3 Mount indicator cartridge on a suitable flat surface using the Clic mounting clamps provided Notes The indicator cartridge must be mounted vertically The indicator cartridge does not have a d...

Page 13: ...vertical position and the drain holes are below the level of the ozone generators ozone outlet fitting One clamp should be located so it fits around the Riser Tube Elbow and the other so it fits aroun...

Page 14: ...the injector manifold until the needle moves into the green zone If the needle is in the red zone on the vacuum in Hg side of the gauge gradually open the ball valve on the injector manifold until the...

Page 15: ...e it will open causing a loss of vacuum A loss of vacuum means ozone cannot flow from the vacuum break which in turn can cause an ozone leak Note If the vacuum break must be refilled with water discon...

Page 16: ...ary by following the steps outlined in the Start Up Calibration section Ozone Generator Indicator Lights Check the Main Power indicator light at the bottom of the ozone generator and Ozone LED s at th...

Page 17: ...one output LED will illuminate when ozone drive is being generated The LED will also pulse as the output increases or decreases with either the Manual Ozone Output Control located on the bottom of the...

Page 18: ...and or operating conditions in the equipment area will dictate the required frequency of this procedure Ozone Generators Cooling Fan Filters Clean or replace the cooling fan filter elements as requir...

Page 19: ...ielectric approximately 1 2 from either end of the glass making sure it is rolled squarely Step 6 Slide the dielectric into the heat sink cathode assembly Seat the dielectric into the O rings of the n...

Page 20: ...normal for some water to be flowing from the injector during this procedure Contact Vessel Cleaning Contact Column only Inspect the diffuser slots at the top of the contact column riser tube If they...

Page 21: ...place compressor or pink or white ATF module as required Replace indicating desiccant Unit is making excessive noise Unit not properly secured to floor Place unit on a flat level surface Shipping dama...

Page 22: ...ing Fault LED The Ozone Output LED s The remote 4 20mA control signal is not Check for loose wires or connections not responding to the remote sensed by the 4 20mA control board 4 20mA control signal...

Page 23: ...libration Debris on seat of vacuum break flapper valve Clean seat of flapper See Maintenance Procedures Annual Low vacuum Hydraulics Pneumatics out of adjustment See Start Up Calibration Steps 1 4 Def...

Page 24: ...ns Shown ClearWater Tech OXS90 Air Prep System with Cover Shown ClearWater Tech OXS90 Air Prep System with out Cover AIR PREP SYSTEM SPECIFICATIONS OXYGEN OUTPUT SCFH OXS90 Workhorse 12c 15 5 h x 17 w...

Page 25: ...Drive Board and Drive Transformer under board Reaction Chamber Power Supply Inline Particulate Filter 4 20mA Control Board Pressure Switch Cover Safety Switch External Loop Remote 4 20mA Control Lead...

Page 26: ...rs Drive Board and Drive Transformer XFMR under boards Inline Particulate Filter Power Supply Pressure Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Air Pre...

Page 27: ...00P RCC10 Dielectric Anode 2 RCC71 Non High Voltage End Cap Contact Dealer High Voltage End Cap Contact Dealer O ring Set ORS40 Drive Module Complete CD2000P DRM60 Drive Module Transformer HVT275 Driv...

Page 28: ...1 Filter Inline particulate filter FUS20 2 Fuse Bussmann MDL 5 5 amp 250VAC Slow Blow Main Power ORG110 4 O ring 2 CD reaction chamber pressurized end cap large ORG120 4 O ring 2 CD reaction chamber p...

Page 29: ...try Module With Fuses High Voltage Transformer Drive Board Remote 4 20mA Ozone Output Control Orange Purple Manual Ozone Output Control Fan Power Supply Cover Safety Switch Power Supply 4 20mA Control...

Page 30: ...afety Switch Power Supply Power Supply Fan Fan 24VDC 24VDC 24VDC 24VDC Manual Ozone Output Control Remote 4 20mA Ozone Output Control Orange Purple External Loop 4 20mA Control Board Variable Output S...

Page 31: ...30 Drive Module Input Voltages Shown Dual HO Drive Module APPENDIX Section E...

Page 32: ...nced with the product and or part must be clearly described The RGA number must appear prominently on the exterior of the shipped box es The product and or part must be packaged either in its original...

Reviews: