background image

 

   

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION PROCEDURES - 

Getting Started              

CHAPTER 3 

Unpacking   

Compare  the  ozone  system  equipment  received  to  the  packing  list  provided.  Before 
beginning  any  installation  procedures,  thoroughly  inspect  all  components  for  damage.  If 
damage  is  noticed,  promptly  notify  the  freight  carrier  and  request  an  on-site  inspection. 
Inspect all packing materials for small parts before discarding. Inspect all plumbing, fittings 
and tubing for packing material that may have become lodged in openings. 

 

Equipment Placement  

• 

When placing the ozone system components in the equipment room, make sure to consider safety,  maintenance 

requirements,  local  building  and  fire  codes,  etc.  The  components  should  be  easily  accessible  by  the  operators, 
including equipment access doors and electrical hook-up boxes. All meters, gauges, indicator lights, and switches 
should  be  visible  and  accessible.  Dimensional  drawings  of  each  air  preparation  system  and  ozone  generator  are 
included in Section A of the Appendix. 

 

• 

The  air  preparation  system  and  ozone  generator  should  be  located  as  close  as  possible  to  the  point  of  ozone 
injection. Ozone is an unstable gas and will begin reverting back to oxygen very quickly. To determine the most 
favorable ozone injection point, the following items should be considered: 

 

 

•   Located 

downstream

 of all other existing water system components. 

 

 

•   Located 

upstream

 of the residual sanitizer injection point (if so equipped). 

•  In  a  Sidestream  plumbing  configuration  (see  Figure  4-1)  with  recirculation,  the  pH  adjustment 

chemical  injection  point  must  be  located 

downstream

  of  the  residual  sanitizer  injection  point  (if  so 

equipped).    

 

 

 

 

 

•   In a Full Flow plumbing configuration (see Figure 4-2) without recirculation, locate 

downstream

 of the 

pH adjustment chemical injection point. 

 

 

•   Adequate protection from weather, dust and excessive heat. 

• 

Like any electronic component, performance and longevity is enhanced by favorable operating conditions. Also, 
since each air preparation system and ozone generator is air-cooled, a relatively dust-free, well-ventilated area is 
required. No caustic chemicals should be stored in the area surrounding the equipment. A minimum clearance of 
six inches from the vents on either side of the ozone generator is required. 

 

• 

The equipment is heavy and requires proper support. Therefore, a clean, dry, level surface should be provided for 

the  air  preparation  system  and  ozone  generator.    These  components  should  be  securely  fastened  to  the  surface 
using the mounting holes and/or tabs provided. 

 

 

• 

The air preparation system and ozone generator are 

not

 designed to withstand outdoor elements, including direct 

contact  with  water  and/or  temperature  extremes.  Therefore,  the  equipment  must  be  installed  in  an  environment 
consistent with the following operating parameters: 

• Ambient temperature range:  20°F to 95°F continuous. If the temperature around the equipment 

consistently exceeds 95°F, additional air-cooling must be provided. 

 

 

• Humidity:  0 – 90% relative humidity, non-condensing environment 

 

 

• Line voltage:  +/-10% of rated input 

 

    

   

 

Note: Equipment installed in extreme environmental conditions will void manufacturer's warranty. 

• 

Allow room for the peripheral equipment (booster pump, injector manifold, contact vessel, etc.).

 

 

 

Summary of Contents for CD1500P

Page 1: ...s a component only Tested and certified by WQA to NSF ANSI 50 as a component only ClearWater Tech LLC Integrated Ozone Systems 850 E Capitolio Way San Luis Obispo Ca 93401 805 549 9724 Fax 805 549 030...

Page 2: ...o achieve the ozone output and longevity of the ozone generator A pounds per square inch PSI regulator must be installed when using plant air feed gas This regulator must be set to a maximum of 10 PSI...

Page 3: ...m of extremely tiny bubbles These bubbles must be as small as possible in order to increase the ratio of bubble surface area to the amount of ozone entering the water Depending on the application and...

Page 4: ...s detectable at very low concentrations 0 02 ppm which is far below OSHA s maximum permissible exposure level of 0 1 ppm HIGH VOLTAGE WARNING CLEARWATER TECH OZONE GENERATORS OPERATE AT HIGH VOLTAGE D...

Page 5: ...ipment 7 The electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422 20 of the National Electrica...

Page 6: ...justment chemical injection point must be located downstream of the residual sanitizer injection point if so equipped In a Full Flow plumbing configuration see Figure 4 2 without recirculation locate...

Page 7: ...ical print or as dictated by equipment layout and serviceability considerations Do not secure booster pump and contact vessel to housekeeping pads at this point Dry fit plumbing as appropriate to insu...

Page 8: ...he two holes for mounting the L bracket to the wall The bracket should be located so that the 6 clamp assembly will be approximately 12 from the top of the contact column Drill a 1 2 hole at each of t...

Page 9: ...Base Flange Gasket Base Flange Nuts Washers 8ea Contact Column Exploded View Figure 4 4 Contact Column Installation Diagram Figure 4 3 6 Clamp Assembly Bolts nuts with bolt Nut washers 2ea Unistrut cu...

Page 10: ...AWG wire located at the bottom panel of the ozone generator see Appendix Section A can be interfaced to any control device i e pressure switch vacuum switch flow switch float switch ORP controller PPM...

Page 11: ...Preparation System Power 120VAC systems only plug the power cord into main power 240VAC systems only the power cord must be hard wired to the main power source Black L1 White L2 N and Green Ground No...

Page 12: ...y Step 3 Mount indicator cartridge on a suitable flat surface using the Clic mounting clamps provided Notes The indicator cartridge must be mounted vertically The indicator cartridge does not have a d...

Page 13: ...vertical position and the drain holes are below the level of the ozone generators ozone outlet fitting One clamp should be located so it fits around the Riser Tube Elbow and the other so it fits aroun...

Page 14: ...the injector manifold until the needle moves into the green zone If the needle is in the red zone on the vacuum in Hg side of the gauge gradually open the ball valve on the injector manifold until the...

Page 15: ...e it will open causing a loss of vacuum A loss of vacuum means ozone cannot flow from the vacuum break which in turn can cause an ozone leak Note If the vacuum break must be refilled with water discon...

Page 16: ...ary by following the steps outlined in the Start Up Calibration section Ozone Generator Indicator Lights Check the Main Power indicator light at the bottom of the ozone generator and Ozone LED s at th...

Page 17: ...one output LED will illuminate when ozone drive is being generated The LED will also pulse as the output increases or decreases with either the Manual Ozone Output Control located on the bottom of the...

Page 18: ...and or operating conditions in the equipment area will dictate the required frequency of this procedure Ozone Generators Cooling Fan Filters Clean or replace the cooling fan filter elements as requir...

Page 19: ...ielectric approximately 1 2 from either end of the glass making sure it is rolled squarely Step 6 Slide the dielectric into the heat sink cathode assembly Seat the dielectric into the O rings of the n...

Page 20: ...normal for some water to be flowing from the injector during this procedure Contact Vessel Cleaning Contact Column only Inspect the diffuser slots at the top of the contact column riser tube If they...

Page 21: ...place compressor or pink or white ATF module as required Replace indicating desiccant Unit is making excessive noise Unit not properly secured to floor Place unit on a flat level surface Shipping dama...

Page 22: ...ing Fault LED The Ozone Output LED s The remote 4 20mA control signal is not Check for loose wires or connections not responding to the remote sensed by the 4 20mA control board 4 20mA control signal...

Page 23: ...libration Debris on seat of vacuum break flapper valve Clean seat of flapper See Maintenance Procedures Annual Low vacuum Hydraulics Pneumatics out of adjustment See Start Up Calibration Steps 1 4 Def...

Page 24: ...ns Shown ClearWater Tech OXS90 Air Prep System with Cover Shown ClearWater Tech OXS90 Air Prep System with out Cover AIR PREP SYSTEM SPECIFICATIONS OXYGEN OUTPUT SCFH OXS90 Workhorse 12c 15 5 h x 17 w...

Page 25: ...Drive Board and Drive Transformer under board Reaction Chamber Power Supply Inline Particulate Filter 4 20mA Control Board Pressure Switch Cover Safety Switch External Loop Remote 4 20mA Control Lead...

Page 26: ...rs Drive Board and Drive Transformer XFMR under boards Inline Particulate Filter Power Supply Pressure Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Air Pre...

Page 27: ...00P RCC10 Dielectric Anode 2 RCC71 Non High Voltage End Cap Contact Dealer High Voltage End Cap Contact Dealer O ring Set ORS40 Drive Module Complete CD2000P DRM60 Drive Module Transformer HVT275 Driv...

Page 28: ...1 Filter Inline particulate filter FUS20 2 Fuse Bussmann MDL 5 5 amp 250VAC Slow Blow Main Power ORG110 4 O ring 2 CD reaction chamber pressurized end cap large ORG120 4 O ring 2 CD reaction chamber p...

Page 29: ...try Module With Fuses High Voltage Transformer Drive Board Remote 4 20mA Ozone Output Control Orange Purple Manual Ozone Output Control Fan Power Supply Cover Safety Switch Power Supply 4 20mA Control...

Page 30: ...afety Switch Power Supply Power Supply Fan Fan 24VDC 24VDC 24VDC 24VDC Manual Ozone Output Control Remote 4 20mA Ozone Output Control Orange Purple External Loop 4 20mA Control Board Variable Output S...

Page 31: ...30 Drive Module Input Voltages Shown Dual HO Drive Module APPENDIX Section E...

Page 32: ...nced with the product and or part must be clearly described The RGA number must appear prominently on the exterior of the shipped box es The product and or part must be packaged either in its original...

Reviews: