11 

Compressor Inlet Filter 
 

SCFH Air Flow Meter   

 

 

 

  Compressor  
  ATF Module (sieve bed) 

           Oxygen Outlet 
 
             Power Switch    

 

 

 

  Hour Meter  

          (if so equipped)   

 

 

 

 

 

         
      Main Power Cord 

INSTALLATION PROCEDURES – 

Pneumatic      

          CHAPTER 6 

 
This  section  outlines  the  steps  required  to  complete  the 
ozone  system  pneumatic  hook-ups.  The  system 
components  include  the  air  preparation  system,  ozone 
generator,  vacuum  break,  and  ozone  injector  manifold 
(see Figure 6-1). The air preparation system provides the 
ozone  generator  with  a  source  of  dry,  oil-free  oxygen-

enriched  air  (90%  +/-  3%  oxygen  purity  at  -100˚F  dew 
point). The air is drawn from the ozone generator (where 
ozone is produced from the oxygen in the air stream) and 
through  the  vacuum  break  by  the  suction  created  at  the 
ozone injector manifold. 

 

Figure 6-1 

 

 

 

 

 

 
 
 
 
 
Hook-Up: Air preparation system-to-ozone generator

 

Step 1:

 Teflon® tape and attach brass barb provided to the PSA oxygen concentrator outlet. 

Step 2:

 Teflon® tape and attach brass barbs to both sides of indicator cartridge (ordered separately). 

Step 3: 

Mount indicator cartridge on  a suitable flat  surface using the Clic®  mounting clamps provided.  

Notes:  The 

indicator  cartridge  must  be  mounted  vertically.    The  indicator  cartridge  does 

not 

have  a  direction  of 

flow.  

An external moisture-indicating cartridge is used as a reference to indicate the quality of the dry air, if 

the air prep system is not operating properly the silica will turn from blue and white in color to all white. See 
Troubleshooting Guide. 

Step 4: 

Using a suitable length of 3/8” braided tubing provided, attach one end of the tubing to the oxygen concentrator 

system  to  one  end  of  the  indicator  cartridge.  Secure  the  tubing  to  the  brass  fittings  with  the  hose  clamps 
provided. 

 

Step 5:

 

Using a suitable length of 3/8” braided tubing, attach tubing to the brass barb located at the other end of the 
indicator cartridge then attach the other end of the tubing to the brass barb located at the bottom of the ozone 
generator. Secure the tubing to the fittings with the hose clamps provided. 

Oxygen Concentrator Detail 

Figure 6-2 
 
 

 

 

 
 

       Booster Pump   Ozone Injector 

 
             Water Flow   

 

 

 
 
 
 
 

       Ozone Generator 

        Air Prep System 

 

 

 

 

 
 
 

            Vacuum Break 
   

      Air Prep In      Ozone Out   

             

Shown: ClearWater Tech CD2000P Ozone System 

 

 

 
 

 

 

 

 

 

 

 

     

Summary of Contents for CD1500P

Page 1: ...s a component only Tested and certified by WQA to NSF ANSI 50 as a component only ClearWater Tech LLC Integrated Ozone Systems 850 E Capitolio Way San Luis Obispo Ca 93401 805 549 9724 Fax 805 549 030...

Page 2: ...o achieve the ozone output and longevity of the ozone generator A pounds per square inch PSI regulator must be installed when using plant air feed gas This regulator must be set to a maximum of 10 PSI...

Page 3: ...m of extremely tiny bubbles These bubbles must be as small as possible in order to increase the ratio of bubble surface area to the amount of ozone entering the water Depending on the application and...

Page 4: ...s detectable at very low concentrations 0 02 ppm which is far below OSHA s maximum permissible exposure level of 0 1 ppm HIGH VOLTAGE WARNING CLEARWATER TECH OZONE GENERATORS OPERATE AT HIGH VOLTAGE D...

Page 5: ...ipment 7 The electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422 20 of the National Electrica...

Page 6: ...justment chemical injection point must be located downstream of the residual sanitizer injection point if so equipped In a Full Flow plumbing configuration see Figure 4 2 without recirculation locate...

Page 7: ...ical print or as dictated by equipment layout and serviceability considerations Do not secure booster pump and contact vessel to housekeeping pads at this point Dry fit plumbing as appropriate to insu...

Page 8: ...he two holes for mounting the L bracket to the wall The bracket should be located so that the 6 clamp assembly will be approximately 12 from the top of the contact column Drill a 1 2 hole at each of t...

Page 9: ...Base Flange Gasket Base Flange Nuts Washers 8ea Contact Column Exploded View Figure 4 4 Contact Column Installation Diagram Figure 4 3 6 Clamp Assembly Bolts nuts with bolt Nut washers 2ea Unistrut cu...

Page 10: ...AWG wire located at the bottom panel of the ozone generator see Appendix Section A can be interfaced to any control device i e pressure switch vacuum switch flow switch float switch ORP controller PPM...

Page 11: ...Preparation System Power 120VAC systems only plug the power cord into main power 240VAC systems only the power cord must be hard wired to the main power source Black L1 White L2 N and Green Ground No...

Page 12: ...y Step 3 Mount indicator cartridge on a suitable flat surface using the Clic mounting clamps provided Notes The indicator cartridge must be mounted vertically The indicator cartridge does not have a d...

Page 13: ...vertical position and the drain holes are below the level of the ozone generators ozone outlet fitting One clamp should be located so it fits around the Riser Tube Elbow and the other so it fits aroun...

Page 14: ...the injector manifold until the needle moves into the green zone If the needle is in the red zone on the vacuum in Hg side of the gauge gradually open the ball valve on the injector manifold until the...

Page 15: ...e it will open causing a loss of vacuum A loss of vacuum means ozone cannot flow from the vacuum break which in turn can cause an ozone leak Note If the vacuum break must be refilled with water discon...

Page 16: ...ary by following the steps outlined in the Start Up Calibration section Ozone Generator Indicator Lights Check the Main Power indicator light at the bottom of the ozone generator and Ozone LED s at th...

Page 17: ...one output LED will illuminate when ozone drive is being generated The LED will also pulse as the output increases or decreases with either the Manual Ozone Output Control located on the bottom of the...

Page 18: ...and or operating conditions in the equipment area will dictate the required frequency of this procedure Ozone Generators Cooling Fan Filters Clean or replace the cooling fan filter elements as requir...

Page 19: ...ielectric approximately 1 2 from either end of the glass making sure it is rolled squarely Step 6 Slide the dielectric into the heat sink cathode assembly Seat the dielectric into the O rings of the n...

Page 20: ...normal for some water to be flowing from the injector during this procedure Contact Vessel Cleaning Contact Column only Inspect the diffuser slots at the top of the contact column riser tube If they...

Page 21: ...place compressor or pink or white ATF module as required Replace indicating desiccant Unit is making excessive noise Unit not properly secured to floor Place unit on a flat level surface Shipping dama...

Page 22: ...ing Fault LED The Ozone Output LED s The remote 4 20mA control signal is not Check for loose wires or connections not responding to the remote sensed by the 4 20mA control board 4 20mA control signal...

Page 23: ...libration Debris on seat of vacuum break flapper valve Clean seat of flapper See Maintenance Procedures Annual Low vacuum Hydraulics Pneumatics out of adjustment See Start Up Calibration Steps 1 4 Def...

Page 24: ...ns Shown ClearWater Tech OXS90 Air Prep System with Cover Shown ClearWater Tech OXS90 Air Prep System with out Cover AIR PREP SYSTEM SPECIFICATIONS OXYGEN OUTPUT SCFH OXS90 Workhorse 12c 15 5 h x 17 w...

Page 25: ...Drive Board and Drive Transformer under board Reaction Chamber Power Supply Inline Particulate Filter 4 20mA Control Board Pressure Switch Cover Safety Switch External Loop Remote 4 20mA Control Lead...

Page 26: ...rs Drive Board and Drive Transformer XFMR under boards Inline Particulate Filter Power Supply Pressure Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Air Pre...

Page 27: ...00P RCC10 Dielectric Anode 2 RCC71 Non High Voltage End Cap Contact Dealer High Voltage End Cap Contact Dealer O ring Set ORS40 Drive Module Complete CD2000P DRM60 Drive Module Transformer HVT275 Driv...

Page 28: ...1 Filter Inline particulate filter FUS20 2 Fuse Bussmann MDL 5 5 amp 250VAC Slow Blow Main Power ORG110 4 O ring 2 CD reaction chamber pressurized end cap large ORG120 4 O ring 2 CD reaction chamber p...

Page 29: ...try Module With Fuses High Voltage Transformer Drive Board Remote 4 20mA Ozone Output Control Orange Purple Manual Ozone Output Control Fan Power Supply Cover Safety Switch Power Supply 4 20mA Control...

Page 30: ...afety Switch Power Supply Power Supply Fan Fan 24VDC 24VDC 24VDC 24VDC Manual Ozone Output Control Remote 4 20mA Ozone Output Control Orange Purple External Loop 4 20mA Control Board Variable Output S...

Page 31: ...30 Drive Module Input Voltages Shown Dual HO Drive Module APPENDIX Section E...

Page 32: ...nced with the product and or part must be clearly described The RGA number must appear prominently on the exterior of the shipped box es The product and or part must be packaged either in its original...