background image

 

   

 

 

 

 

 

 

 

 

             

Pneumatic

  (continued) 

12 

Hook-Ups: Ozone generator-to-vacuum break & vacuum break-to-injector manifold 

The ClearWater Tech vacuum break provides a positive atmospheric “break” between the ozone injector manifold and the 
ozone generator, preventing water from flowing back into the ozone generator should the venturi check valve fail. Under 
normal operating conditions, the vacuum break's flapper valve (see Figure 6-3) is closed, allowing the vacuum created by 
the  venturi  to  draw  the  output  gas  from  the  ozone  generator.    If  the  check  valve  at  the  venturi  begins  to  leak  or  fails 
completely,  vacuum  is  interrupted  and  water  will  flow  toward  the  ozone  generator.  With  the  vacuum  break  properly 
installed  between  the  venturi  and  the  ozone  generator,  the  water  will  flow  down  the  riser  tube  (away  from  the  ozone 
generator)  and  out  to  drain,  protecting  the  ozone  generator  from  potential  water  damage. 

Note:  All  Teflon®  delivery 

lines  that  are  secured  by  a  stainless  steel  compression  fittings  require  a  tubing  insert  (inserts  are  located  in  the 
Vacuum  Break  parts  bag).  This  insert  will  prevent  crushing  of  the  tubing,  which  may  create  an  ozone  leak.    All 
stainless steel compression fittings must be tightened no more than 1-1/4 turns past finger tight.

 

Step 1: 

 

Select a suitable vertical surface that is accessible and in close proximity to both the ozone generator and the 

ozone injector manifold. 

Step  2: 

Install  the  two  Clic®  mounting  clamps  provided  onto  the  vertical  surface  so  that  the  vacuum  break  is  in  a 

vertical position and the drain holes are 

below

 the level of the ozone generators ozone outlet fitting. One clamp 

should  be  located  so  it  fits  around  the  Riser  Tube  Elbow,  and  the  other  so  it  fits  around  the  bottom  of  the 
Lower Tee (see Figure 6-3). 

Step 3:

 

Remove  the  Fill  Port  Cap  located  on  top  of  the  Riser  Tube  and  fill  the  Riser  Tube  with  clean  water  (no 
particulate matter) until "Fill Level" line indicated in Figure 6-3. 

Step 4:

 

Re-install the Fill Port Cap, using pliers or a wrench to tighten. 

Note:

 

Do not over tighten as damage to PVC 

fittings may occur.

 

Step 6:

 

Connect  one  end  of  a  suitable  length  of  Teflon®  ozone  delivery  line  to  the  ozone  outlet  needle  valve  (see 
Appendix,  Section  A). 

Notes:  The  compression  fitting  ferrules  are  zip  tied  to  the  ozone  outlet  needle 

valve. 

Attach  the  other  end  of  the  Teflon®  delivery  line  to  the  fitting  threaded  into  the  Upper  Tee.    As  an 

additional  backflow  prevention  measure,  loop  this  length  of  tubing  as  high  as  is  practical  between  the  two 
connection points.

 

Step 7:  

Connect one end of a second length of Teflon® delivery line to the fitting threaded into the Lower  Tee.  The 
other end of the delivery line will be attached to the fitting located on top of the check valve assembly, in step 
6 of Chapter 7, “Start-up and Calibration Procedures.”

 

Step 8:

 

Adjustments to the valve on the ozone injector manifold will be necessary. These steps are covered in Chapter 
7, “Start-up and Calibration Procedures.” 

Vacuum Break Detail 

Figure 6-3 

   

 
 
 
 
 
 

  

 
 
 

 

 
 

 

   

 

    Ozone Generator 

 

   

 

Ozone Flow  

 

 

           Fill Port Cap 

          
          Upper Tee 

 

     Ozone Outlet 

Ozone Flow 

 
Lower Tee  

    Riser Tube  

 Drain Barb 

       Check Valve Assembly 

 

        Overflow Tube 

                          Mounting Clamps 

   Fill  

       

  

 Level 

 

 

           Riser Elbow 

     Ozone Injection Manifold 

 Flapper Check Valve 

            

 

Summary of Contents for CD1500P

Page 1: ...s a component only Tested and certified by WQA to NSF ANSI 50 as a component only ClearWater Tech LLC Integrated Ozone Systems 850 E Capitolio Way San Luis Obispo Ca 93401 805 549 9724 Fax 805 549 030...

Page 2: ...o achieve the ozone output and longevity of the ozone generator A pounds per square inch PSI regulator must be installed when using plant air feed gas This regulator must be set to a maximum of 10 PSI...

Page 3: ...m of extremely tiny bubbles These bubbles must be as small as possible in order to increase the ratio of bubble surface area to the amount of ozone entering the water Depending on the application and...

Page 4: ...s detectable at very low concentrations 0 02 ppm which is far below OSHA s maximum permissible exposure level of 0 1 ppm HIGH VOLTAGE WARNING CLEARWATER TECH OZONE GENERATORS OPERATE AT HIGH VOLTAGE D...

Page 5: ...ipment 7 The electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422 20 of the National Electrica...

Page 6: ...justment chemical injection point must be located downstream of the residual sanitizer injection point if so equipped In a Full Flow plumbing configuration see Figure 4 2 without recirculation locate...

Page 7: ...ical print or as dictated by equipment layout and serviceability considerations Do not secure booster pump and contact vessel to housekeeping pads at this point Dry fit plumbing as appropriate to insu...

Page 8: ...he two holes for mounting the L bracket to the wall The bracket should be located so that the 6 clamp assembly will be approximately 12 from the top of the contact column Drill a 1 2 hole at each of t...

Page 9: ...Base Flange Gasket Base Flange Nuts Washers 8ea Contact Column Exploded View Figure 4 4 Contact Column Installation Diagram Figure 4 3 6 Clamp Assembly Bolts nuts with bolt Nut washers 2ea Unistrut cu...

Page 10: ...AWG wire located at the bottom panel of the ozone generator see Appendix Section A can be interfaced to any control device i e pressure switch vacuum switch flow switch float switch ORP controller PPM...

Page 11: ...Preparation System Power 120VAC systems only plug the power cord into main power 240VAC systems only the power cord must be hard wired to the main power source Black L1 White L2 N and Green Ground No...

Page 12: ...y Step 3 Mount indicator cartridge on a suitable flat surface using the Clic mounting clamps provided Notes The indicator cartridge must be mounted vertically The indicator cartridge does not have a d...

Page 13: ...vertical position and the drain holes are below the level of the ozone generators ozone outlet fitting One clamp should be located so it fits around the Riser Tube Elbow and the other so it fits aroun...

Page 14: ...the injector manifold until the needle moves into the green zone If the needle is in the red zone on the vacuum in Hg side of the gauge gradually open the ball valve on the injector manifold until the...

Page 15: ...e it will open causing a loss of vacuum A loss of vacuum means ozone cannot flow from the vacuum break which in turn can cause an ozone leak Note If the vacuum break must be refilled with water discon...

Page 16: ...ary by following the steps outlined in the Start Up Calibration section Ozone Generator Indicator Lights Check the Main Power indicator light at the bottom of the ozone generator and Ozone LED s at th...

Page 17: ...one output LED will illuminate when ozone drive is being generated The LED will also pulse as the output increases or decreases with either the Manual Ozone Output Control located on the bottom of the...

Page 18: ...and or operating conditions in the equipment area will dictate the required frequency of this procedure Ozone Generators Cooling Fan Filters Clean or replace the cooling fan filter elements as requir...

Page 19: ...ielectric approximately 1 2 from either end of the glass making sure it is rolled squarely Step 6 Slide the dielectric into the heat sink cathode assembly Seat the dielectric into the O rings of the n...

Page 20: ...normal for some water to be flowing from the injector during this procedure Contact Vessel Cleaning Contact Column only Inspect the diffuser slots at the top of the contact column riser tube If they...

Page 21: ...place compressor or pink or white ATF module as required Replace indicating desiccant Unit is making excessive noise Unit not properly secured to floor Place unit on a flat level surface Shipping dama...

Page 22: ...ing Fault LED The Ozone Output LED s The remote 4 20mA control signal is not Check for loose wires or connections not responding to the remote sensed by the 4 20mA control board 4 20mA control signal...

Page 23: ...libration Debris on seat of vacuum break flapper valve Clean seat of flapper See Maintenance Procedures Annual Low vacuum Hydraulics Pneumatics out of adjustment See Start Up Calibration Steps 1 4 Def...

Page 24: ...ns Shown ClearWater Tech OXS90 Air Prep System with Cover Shown ClearWater Tech OXS90 Air Prep System with out Cover AIR PREP SYSTEM SPECIFICATIONS OXYGEN OUTPUT SCFH OXS90 Workhorse 12c 15 5 h x 17 w...

Page 25: ...Drive Board and Drive Transformer under board Reaction Chamber Power Supply Inline Particulate Filter 4 20mA Control Board Pressure Switch Cover Safety Switch External Loop Remote 4 20mA Control Lead...

Page 26: ...rs Drive Board and Drive Transformer XFMR under boards Inline Particulate Filter Power Supply Pressure Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Air Pre...

Page 27: ...00P RCC10 Dielectric Anode 2 RCC71 Non High Voltage End Cap Contact Dealer High Voltage End Cap Contact Dealer O ring Set ORS40 Drive Module Complete CD2000P DRM60 Drive Module Transformer HVT275 Driv...

Page 28: ...1 Filter Inline particulate filter FUS20 2 Fuse Bussmann MDL 5 5 amp 250VAC Slow Blow Main Power ORG110 4 O ring 2 CD reaction chamber pressurized end cap large ORG120 4 O ring 2 CD reaction chamber p...

Page 29: ...try Module With Fuses High Voltage Transformer Drive Board Remote 4 20mA Ozone Output Control Orange Purple Manual Ozone Output Control Fan Power Supply Cover Safety Switch Power Supply 4 20mA Control...

Page 30: ...afety Switch Power Supply Power Supply Fan Fan 24VDC 24VDC 24VDC 24VDC Manual Ozone Output Control Remote 4 20mA Ozone Output Control Orange Purple External Loop 4 20mA Control Board Variable Output S...

Page 31: ...30 Drive Module Input Voltages Shown Dual HO Drive Module APPENDIX Section E...

Page 32: ...nced with the product and or part must be clearly described The RGA number must appear prominently on the exterior of the shipped box es The product and or part must be packaged either in its original...

Reviews: