June 2002
Chapter 14 Alarm Troubleshooting
Alarm Procedures
14.4.90 MFGMEM
•
Critical, Service-Affecting
The manufacturing data memory failure (MFGMEM) alarm raises if the ONS 15327 cannot access the
data in the erasable programmable read-only memory (EPROM). Either the memory module on the
component failed or the XTC lost the ability to read that module. The EPROM stores manufacturing data
that is needed for both compatibility and inventory issues. The EPROM on the alarm interface panel
(AIP) also stores the MAC address. An inability to read a valid MAC address disrupts IP connectivity
and gray out the ONS 15327 icon on the CTC network view.
Procedure: Clear the MFGMEM Alarm on the AIP, Fan Tray, or Backplane
Step 1
Do a software-initiated system reset on the XTC by referring to the
Step 2
If the alarm does not clear, do a card pull reset on the XTC by referring to the
Step 3
If the alarm does not clear, physically replace the standby XTC card on the ONS 15327 with a new XTC
card:
a.
Open the XTC card ejectors.
b.
Slide the card out of the slot. This raises the
IMPROPRMVL
alarm which clears when the upgrade is
complete.
c.
Open the ejectors on the XTC card.
d.
Slide the XTC card into the slot along the guide rails.
e.
Close the ejectors.
Note
It takes approximately 30 minutes for the active XTC to transfer the system software to the
newly installed XTC. Software transfer occurs in instances where different software
versions exist on the two cards. During this operation, the LEDs on the XTC flash Fail and
then the Active/Standby LED flashes. When the transfer completes, the XTC reboots and
goes into Standby mode after approximately three minutes.
Step 4
Right-click the active XTC card to reveal a drop-down menu.
Step 5
Click
Reset Card
.
Wait for the XTC to reboot. The ONS 15327 switches the standby XTC card to active mode.
Step 6
Verify that the remaining XTC card is now in standby mode (the ACT/STBY LED changes to amber).
Step 7
Physically replace the remaining XTC card with the second XTC card.
a.
Open the XTC card ejectors.
b.
Slide the card out of the slot.
c.
Open the ejectors on the XTC card.
d.
Slide the XTC card into the slot along the guide rails.
e.
Close the ejectors.
Summary of Contents for ONS 15327
Page 22: ...Contents xxii Cisco ONS 15327 User Documentation June 2002 I N D E X ...
Page 30: ...Figures xxviii Cisco ONS 15327 User Documentation June 2002 ...
Page 44: ...Procedures xlii Cisco ONS 15454 Installation and Operations Guide R3 2 June 2002 ...
Page 540: ...Glossary GL 16 Cisco ONS 15327 User Documentation R3 3 June 2002 ...