3-2
Cisco AC/DC Power System User Guide, R1.0
May 2006
Chapter 3 Component Replacement
3.2.1 Replace the 1 RU Distribution Shelf
Figure 3-1
Removing the 1 RU DC Cable
Step 5
Locate the distribution alarm cable at the rear of the 1RU DC Distribution Shelf.
Step 6
Remove the 10 pin Molex™ alarm cable by squeezing the top and pulling the cable away from the shelf
(
Figure 3-1
#1).
Step 7
Locate the four 6AWG (16mm²) power cables provided at the rear of the 1RU Distribution Shelf.
Step 8
Remove the power cables by pulling them out and away from the 1RU Distribution Shelf (
Figure 3-1
#3).
Note
Cover the connectors to insulate the live current on the lugs.
Step 9
Locate the ground cable attached to the #10 studs at the rear of the 1RU Distribution Shelf.
Step 10
Using an 8mm socket or wrench remove the nuts and the ground cable (
Figure 3-1
#4).
Step 11
Remove the four screws that mount the shelf to the cabinet/rack (
Figure 3-2
).
124781
Summary of Contents for 124778
Page 6: ...Contents vi Cisco AC DC Power System User Guide R1 0 May 2006 ...
Page 10: ...Tables x Cisco AC DC Power System User Guide R1 0 May 2006 ...
Page 76: ...5 4 Cisco AC DC Power System User Guide R1 0 May 2006 Chapter 5 System Troubleshooting ...
Page 78: ...6 2 Cisco AC DC Power System User Guide R1 0 May 2006 Chapter 6 System Parts List ...
Page 86: ...A 8 Cisco AC DC Power System User Guide R1 0 May 2006 Appendix A Translated Safety Warnings ...