2-25
Cisco AC/DC Power System User Guide, R1.0
May 2006
Chapter 2 System Installation
2.5.1 Install GMT Fuse Connections
2.5.1 Install GMT Fuse Connections
Load connections to the GMT fuse panel are made using spring loaded terminals that do not require the
use of connection lugs.
Step 1
Locate the GMT fuse connections by removing the controller faceplate (
Figure 2-19
) and sliding the
GMT drawer out (
Figure 2-22
).
Figure 2-22
GMT Drawer
Step 2
Route the GMT load-and-return cabling from the rear of the system shelf (leaving enough of a service
loop to allow the drawer to slide out) through the fuse panel channel and secure using the supplied
tie-downs.
Step 3
Connect the wires to the appropriate terminal by using a flat screwdriver to open the terminal
(
Figure 2-23
) and inserting the appropriate cable into the spring-loaded terminals. Terminals correspond
to fuses: Side A (1-5) and Side B (1-5) from left to right (viewed from the front of the system).
14 AWG (2.5mm²)
10A GMT Fuses
14 AWG (2.5mm²)
15A GMT Fuses
Table 2-7
Recommended Wire Sizes (continued)
Wire Gauge Stranded
Applications
Summary of Contents for 124778
Page 6: ...Contents vi Cisco AC DC Power System User Guide R1 0 May 2006 ...
Page 10: ...Tables x Cisco AC DC Power System User Guide R1 0 May 2006 ...
Page 76: ...5 4 Cisco AC DC Power System User Guide R1 0 May 2006 Chapter 5 System Troubleshooting ...
Page 78: ...6 2 Cisco AC DC Power System User Guide R1 0 May 2006 Chapter 6 System Parts List ...
Page 86: ...A 8 Cisco AC DC Power System User Guide R1 0 May 2006 Appendix A Translated Safety Warnings ...
Page 96: ...A 18 Cisco AC DC Power System User Guide R1 0 May 2006 Appendix A Translated Safety Warnings ...