2-27
Cisco AC/DC Power System User Guide, R1.0
May 2006
Chapter 2 System Installation
2.5.2 Install 1 RU Distribution Shelf Load Connections
Step 1
Select the wire gauge for the application. See
Table 2-7 on page 2-24
for wiring information.
Step 2
Locate the load-and-return connections at the rear of the 1 RU Distribution Shelf (
Figure 2-25
).
Step 3
Remove the Phoenix Contact PC6™ connectors from the 1 RU Distribution Shelf by loosening the flat
screws and pulling the connectors away from the 1 RU Distribution Shelf (
Figure 2-25
#1).
Figure 2-25
Installing Load Connections
Step 4
Connect the wires to the appropriate terminal for the load-and-return connections by inserting and then
tightening the connector (Phoenix Contact PC6™ connectors) (
Figure 2-25
#2, #3). Allow enough of a
service loop to allow for the removal of the 1 RU Distribution Shelf.
Step 5
Reinstall the Phoenix Contact PC6™ connector to the 1 RU Distribution Shelf (
Figure 2-25
#3).
Step 6
Reconnect to the 1RU Distribution Shelf (
Figure 2-25
#4).
Step 7
Connect the load-and-return cables to the equipment that requires the supplied DC Power per that
equipment’s specifications.
Return
Load
A1
B1
B2
A2
124782
Summary of Contents for 124778
Page 6: ...Contents vi Cisco AC DC Power System User Guide R1 0 May 2006 ...
Page 10: ...Tables x Cisco AC DC Power System User Guide R1 0 May 2006 ...
Page 76: ...5 4 Cisco AC DC Power System User Guide R1 0 May 2006 Chapter 5 System Troubleshooting ...
Page 78: ...6 2 Cisco AC DC Power System User Guide R1 0 May 2006 Chapter 6 System Parts List ...
Page 86: ...A 8 Cisco AC DC Power System User Guide R1 0 May 2006 Appendix A Translated Safety Warnings ...
Page 96: ...A 18 Cisco AC DC Power System User Guide R1 0 May 2006 Appendix A Translated Safety Warnings ...