61
Instruction Manual
AFQm
Table 23 (Cont�) : Warnings messages�
Alarm and event messages
Corrective
action
Confirm that the connections are correct.
Reverse power
Description
The power value measured is negative (generated power), which might indicate that the transformers
have been connected inversely.
Corrective
action
Confirm that the connections are correct.
Wxxx
Description
Internal error.
Corrective
action
Contact the Technical Assistance Service.
Parallel filter in alarm
Description
This is a fault in one or more slaves.
Corrective
action
The device does not stop and adjusts its operation to the number of available slaves. On the slave
device status screen, “
” you can view the status and alarms for each
filter. If there is a communications error with any of the slaves, stop the devices and check the com-
munications wiring.
6�18�- TEMPERATURE
Note:
This screen is not visible on the
“slave”
devices.
, displays the device’s temperature range for inductances and IGBTs.
Figure 62: Temperature�
The screen displays:
Ok
, correct temperature.
Hi
, high temperature.
Low
, low temperature.
Use the
and
keys to navigate through the different display screens.
Summary of Contents for AFQm-3WF-030M-480
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 21A...
Page 2: ...2 AFQm Instruction Manual...
Page 111: ...111 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 108 Dimensions Cabinet type AFQm...
Page 113: ...113 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 114: ...114 AFQm Instruction Manual...
Page 115: ...115 Instruction Manual AFQm...