36
AFQm
Instruction Manual
3�8�1�- CONNECTING INDIVIDUAL DEVICES
To connect multiple individual devices in parallel, follow these steps:
1�-
Select the device that will operate as the “
master
”.
2�-
Connect the “
master
” device. The current transformers are only connected to the “
master
” device.
3�-
Connect all of the “
slave
” devices.
Note:
Each devices must feature the protection elements indicated in section
4�-
Connect all of the devices using the communication cables (
).
Table 16: Communication cable, devices in parallel�
Communication cable
RJ11 connector
Pinout
4
3 2
1
1:
Not connected.
2:
CAN A
3:
CAN B
4:
Not connected.
Note:
The communication cable must be a CAT 5 cable or higher.
Connect the
OUT
terminal from the “
master
” filter to the
IN
terminal from the second filter, the
OUT
terminal from the second filter to the
IN
terminal of the third, and so on (
OUT
IN
2
3
2
3
ON
R
BUS
OUT
IN
2
3
2
3
ON
R
BUS
ON
R
BUS
Figure 30:Connecting 3 devices in parallel, using the communication cable�
5�-
Configure the installation in the “
master
” device (see
)
6.-
Complete the configuration of the slave devices
(see
).
7.-
Enable the terminator switch for parallel connection,
R
BUS
in the bus end devices only. Then disable in the other devices.
Summary of Contents for AFQm-3WF-030M-480
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 21A...
Page 2: ...2 AFQm Instruction Manual...
Page 111: ...111 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 108 Dimensions Cabinet type AFQm...
Page 113: ...113 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 114: ...114 AFQm Instruction Manual...
Page 115: ...115 Instruction Manual AFQm...