60
AFQm
Instruction Manual
Table 23 (Cont�) : Warnings messages�
Alarm and event messages
Load polarity
Description
Detection of an error in the load polarity.
Corrective
action
Check the transformer connections. See section
“7.9.- TRANSFORMER CONFIGURATION”
Disabled X harmonic
Description
Harmonic X has been disabled due to resonance.
Corrective
action
The resonance detection function can be activated erroneously in installations with a very high volt-
age THD. Contact the
TAS
.
Annual maintenance
Description
A year has passed since the last maintenance procedure was carried out and the maintenance meter
was reset.
Corrective
action
Perform the annual maintenance procedure and reset the maintenance meter. (see
)
Fan maintenance
Description
Fans have been operating for over 40,000 hours; they must be replaced and the maintenance meter
must be reset.
Corrective
action
Replace the fans and reset the maintenance meter. (see “
Fan deterioration
Description
Deterioration in the ventilation capacity of the system has been detected.
Corrective
action
Check that the fans are clean. Perform the periodic maintenance tasks. Replace the fans if this does
not solve the problem. (see “
Mains voltage out of limits
Description
Mains voltage below the minimum
Corrective
action
This alert may be associated with transients and noise in the power supply voltage, or with incorrect
mains frequency values. Check the configuration. Check the quality of the power supply voltage. If it
continues, contact the
TAS�
Min temperature
Description
Temperature below the minimum operating value
Corrective
action
Wait for the environmental conditions to meet the requirements. If the alarm continues, contact the
TAS�
Mains frequency limits
Description
Main frequency out of the limits
Corrective
action
This alert may be associated with transients and noise in the power supply voltage, or with incorrect
mains frequency values. Check the configuration. Check the quality of the power supply voltage. If it
continues, contact the
TAS�
Minimum current
Description
Mains current below the programmed level.
Corrective
action
Check the configuration.
Maximum load
Description
Filter working at full load
Corrective
action
No action is necessary.
Low power factor
Description
The power factor value measured is less than 0.7, which might indicate a connection error in the
measuring transformers, where the voltage phases do not correspond to the current phases.
Summary of Contents for AFQm-3WF-030M-480
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 21A...
Page 2: ...2 AFQm Instruction Manual...
Page 111: ...111 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 108 Dimensions Cabinet type AFQm...
Page 113: ...113 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 114: ...114 AFQm Instruction Manual...
Page 115: ...115 Instruction Manual AFQm...