57
Instruction Manual
AFQm
6�16�- ALARMS
Note:
This screen is not visible on the
“slave”
devices.
, the alarms that have occurred are shown.
Figure 58: Alarms�
A brief description of the alarm is displayed on the screen, as well as the date and time at which it
occurred.
Press the
key to delete the alarm log.
shows the messages that could appear on the device.
If the cause of the alarm disappears, the device will be reconnected automatically.
If the same alarm is triggered 5 times during a 1-hour period, the automatic device reconnection
function will be disabled.
The
key rearms the device if the cause of the alarm has disappeared or has been resolved.
If the device remains in a permanent alarm state, the screen shown in
, is displayed.
Figure 59: Permanent alarms�
If the display has entered energy saving mode, it is automatically disabled. The alarm screen disap-
pears when the display is touched.