110
AFQm
Instruction Manual
AFQm-xxx-070C, AFQm-xxx-100C, AFQm-xxx-140C, AFQm-xxx-200C,
AFQm-xxx-210C, AFQm-xxx-280C, AFQm-xxx-300C, AFQm-xxx-400C
Dimensions (mm)
Weight
AFQm-xxx-070C
AFQm-xxx-100C
AFQm-xxx-140C
AFQm-xxx-200C
192 kg
190 kg
249 kg
245 kg
AFQm-xxx-210C
AFQm-xxx-280C
AFQm-xxx-300C
AFQm-xxx-400C
306 kg
363 kg
300 kg
355 kg
Enclosure
Free-standing sheet steel cabinet, for installation indoors, without removable parts.
Noise
AFQm-xxx-070C
AFQm-xxx-100C
AFQm-xxx-140C
AFQm-xxx-200C
< 70 dBA
< 60 dBA
< 73 dBA
< 63 dBA
AFQm-xxx-210C
AFQm-xxx-280C
AFQm-xxx-300C
AFQm-xxx-400C
< 76 dBA
< 79 dBA
< 66 dBA
< 69 dBA
Connections
Current
Type
Spring
2.5 mm
2
Earth
(10)
Type
Ring terminal
8 mm
10 Nm
Hex 13 mm
Ethernet
Type
RJ-45
Mains
Filter
Bar
(11)
Drill
Screw
Terminal
width
AFQm-xxx-070C
30x3
1xM10
M10 8.8
≤ 32 mm
45 Nm
AFQm-xxx-100C
AFQm-xxx-140C
40x5
≤ 37 mm
AFQm-xxx-200C
AFQm-xxx-210C
AFQm-xxx-280C
AFQm-xxx-300C
40x10
AFQm-xxx-400C
Neutral
AFQm-xxx-070C
50x10
2xM10
M10 8.8
≤ 32 mm
45 Nm
AFQm-xxx-100C
AFQm-xxx-140C
80x10
≤ 37 mm
AFQm-xxx-200C
AFQm-xxx-210C
AFQm-xxx-280C
AFQm-xxx-300C
100x10
3xM10
AFQm-xxx-400C
(10)
If the phase conductors exceed 32 mm
2
, the earth conductor can be the half of the cross-section of the phase conduc-
tors.
(11)
The connection bars allow the cables to be placed on both sides, and two cables may be routed through each drill hole.
Summary of Contents for AFQm-3WF-030M-480
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 21A...
Page 2: ...2 AFQm Instruction Manual...
Page 111: ...111 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 108 Dimensions Cabinet type AFQm...
Page 113: ...113 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 114: ...114 AFQm Instruction Manual...
Page 115: ...115 Instruction Manual AFQm...