75
Instruction Manual
AFQm
●
Invert
This parameter is used to select the phase whose filter is going to switch the current direction of the
load measurement transformer, so installation faults may be corrected.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.
7�10�- ALARMS
Note:
This screen is not visible on the
“slave”
devices.
, the enabling or disabling of the resonance alarm is selected.
Figure 79: Configuration screen: Alarms�
If the control algorithm was selected in the
Frequency mode
and this alarm is
enabled
, when the de-
vice detects a potential resonance on an harmonic, it disables said harmonic and generates an alarm,
but it continues filtering the rest of the harmonics.
If the alarm is
disabled
, the device may interpret a resonance as an overload and continue filtering the
harmonic.
This option is
enabled
by default and it is recommended not to disable it.
Before
disabling
the resonance alarm, it is essential to make sure there is no resonat-
ing current between the active filter and the load. Resonating currents can damage the
active filter and other devices connected to the installation.
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.
Summary of Contents for AFQm-3WF-030M-480
Page 1: ...INSTRUCTION MANUAL Active Parallel Multi Function Filter AFQm M217B01 03 21A...
Page 2: ...2 AFQm Instruction Manual...
Page 111: ...111 Instruction Manual AFQm 608 812 1755 665 465 1890 Figure 108 Dimensions Cabinet type AFQm...
Page 113: ...113 Instruction Manual AFQm 14 CE CERTIFICATE...
Page 114: ...114 AFQm Instruction Manual...
Page 115: ...115 Instruction Manual AFQm...