89
Instruction Manual
AFQevo
7�-
Remove the remaining fans by repeating step
6
.
8�-
Insert the fan, taking care not to pinch any cable, and re-tighten the 2 screws. Repeat this
process for the remaining fans. Connect the fans’ cables to the connector.
9�-
Install the device’s upper cover by tightening the 6 fixing screws.
Note:
Recommended tightening torque:
1�5 Nm
10�-
Re-connect to the electrical network and start up the
AFQevo
.
11�-
Check that the fans are working properly.
To do this, go to the maintenance screen, via the configuration screen, by pressing the
key and entering the password to log into the maintenance screen
(
Maintenance password :
8888).
The screen in
is displayed.
Figure 89: Maintenance screen�
Checking the operation of the fans:
A�-
Press the key
, the fan starts to operate at a rotation speed of 50%; check that
it is working properly.
Press the key
, to stop the fan.
B�-
Press the key
, the fan starts to operate at a rotation speed of 100%; check that
it is working properly.
Press the key
, to stop the fan.
Note:
The fans will stop if the key
is not pressed after 1 minute.
12�-
Reset the fans’ maintenance meter by pressing the
key.