15
Instruction Manual
AFQevo
If the device is installed in cabinets with a smaller available space, or with a cover on the back,
we recommend using the deflectors that are supplied, which direct the airflows upwards, re
-
sulting in the air flowing out of the top of the cabinet. The top of the cabinet must enable proper
ventilation.
It should be noted that, depending on the installation conditions in the cabinet and in the room
where this is placed, the outflows of hot air may be sucked back in by the device’s fans, causing
a feedback of hot air that will lower the performance of the device.
It is also necessary to bear in mind the power dissipated by the device when choosing where
to install it, to ensure proper air recirculation, to make sure that the intake air is a suitable tem-
perature.
Table 7: Ventilation distances: AFQe-xxx-100R�
Ventilation distances :
AFQe-xxx-100R
600 mm
(1)
600 mm
600 mm
(1)
With deflectors installed.
3�2�1�3�- AFQevo cabinet-type: AFQe-xxx-100C and AFQe-xxx-200C
The cabinet-type
AFQevo
uses a forced ventilation cooling system, with an air inlet on the front
panel and an air outlet at the back of the device.
The ventilation grille at the top must not be blocked, leaving enough space to the ceiling to allow
the heat to dissipate. The distance depends on the characteristics of the installation site.
There is no need to leave space between the sides or at the back of the cabinet; they can be
installed next to other cabinets and against a wall.
Table 8: Ventilation distances: AFQe-xxx-100C and AFQe-xxx-200C
Ventilation distances : cabinet type
AFQevo
Depends on the
characteristics of the site
600 mm